ATLAS D 30 SI UNIT
Checks during operation
•
Ignite the appliance as described in sec. 2.3.
•
Check that the fuel circuit and water systems are airtight.
•
Check the efficiency of the flue and air-fume ducts while the boiler is working.
•
Check that the water is circulating properly between the boiler and the systems.
•
Check the proper ignition of the boiler by performing various tests, turning it on and
off with the room thermostat or remote control.
•
Check that the burner door and fume chamber are tight.
•
Check that the burner works properly.
•
Analyse the combustion (with the boiler unit stable) and check that the content of
CO
in the fumes is between 11% and 12%.
2
•
Check the parameters are programmed correctly and perform any required custom-
ization (compensation curve, power, temperatures, etc.).
4.3 Maintenance
Periodical check
To ensure correct operation of the unit over time, have qualified personnel carry out a
yearly check, providing for the following:
•
The control and safety devices must function correctly.
•
The fume exhaust circuit must be perfectly efficient.
•
Check there are no obstructions or dents in the fuel supply and return pipes.
•
Clean the filter of the fuel suction line.
•
Measure the correct fuel consumption
•
Clean the combustion head in the fuel outlet zone, on the swirl disc.
•
Leave the burner running at full rate for approximately ten minutes, then analyse
the combustion, checking:
-
All the elements specified in this manual are set correctly
-
Temperatures of the fumes at the flue
-
CO2 percentage content
•
The air-fume end piece and ducts must be free of obstructions and leaks
•
The burner and exchanger must be clean and free of deposits. For possible clean-
ing do not use chemical products or wire brushes.
•
The gas and water systems must be airtight.
•
The water pressure in the cold water system must be approx. 1 bar; otherwise, bring
it to that value.
•
The circulating pump must not be blocked.
•
The expansion tank must be filled.
•
Check the magnesium anode and replace it if necessary.
The boiler casing, control panel and aesthetic parts can be cleaned with a soft
A
and damp cloth, if necessary soaked in soapy water. Do not use any abrasive
detergents and solvents.
Boiler cleaning
1.
Disconnect the power supply to the boiler.
2.
Remove the front top and bottom panel.
3.
Open the door by undoing the knobs.
4.
Clean the inside of the boiler and the entire path of exhaust fumes, using a tube
brush or compressed air.
5.
Then close the door, securing it with the knob.
To clean the burner, refer to the Manufacturer's instructions.
Burner disassembly
•
Remove the cover (B) by undoing the screw (A), thereby making all the accessories
accessible.
•
Undo the nut (C) and position the burner so as to access the nozzle.
fig. 35 - Burner disassembly
All manuals and user guides at all-guides.com
4.4 Troubleshooting
Diagnostics
The boiler is equipped with an advanced self-diagnosis system. In case of a boiler fault,
the display will flash together with the fault symbol (detail 22 - fig. 1) indicating the fault
code.
There are faults that cause permanent shutdowns (marked with the letter "A"): to restore
operation press the RESET button (detail 8 - fig. 1) for 1 second or use the RESET on
the remote timer control (optional) if installed; if the boiler does not restart it is necessary
to eliminate the fault indicated in the operation LEDs.
Other faults cause temporary shutdowns (marked with the letter "F") which are automat-
ically reset as soon as the value returns within the boiler's normal working range.
Table. 8 - List of faults
Fault
code
A01
A02
A03
A04
F07
F09
F10
F11
F12
F14
F16
F34
F35
F37
F39
F40
A41
F42
F47
cod. 3540S516 - Rev. 01 - 03/2015
Fault
Possible cause
Pump blocked
Faulty electric motor
Faulty oil valve
No fuel in tank, or water on bottom
Oil line feed valves closed
Dirty filters (line-pump-nozzle)
Pump unprimed
Ignition electrodes dirty or not properly
adjusted
Nozzle clogged, dirty or deformed
Burner block
Unsuitable head and shutter adjustments Adjust
Faulty electrodes or earthed
Faulty ignition transformer
Faulty electrode wires or earthed
Electrode wires deformed by high temper-
ature
Faulty valve or transformer electrical con-
nections
Broken pump-motor joint
Pump inlet connected to return pipe
Faulty photoresistance
Dirty photoresistance
Photoresistance short circuit
Flame present signal
Extraneous light strikes the photoresist-
with burner off
ance
Heating sensor damaged
Overtemperature pro-
tection activation
No water circulation in the system
Air in the system
Card parameter fault
Wrong card parameter setting
Preheater fault (the
Preheater fault
contact does not close
Wiring disconnected
in 120 seconds)
Card parameter fault
Wrong card parameter setting
Sensor damaged
Delivery sensor 1 fault
Wiring shorted
Wiring disconnected
Card parameter fault
Wrong card parameter setting
Card parameter fault
Wrong card parameter setting
Sensor damaged
Delivery sensor 2 fault
Wiring shorted
Wiring disconnected
Card parameter fault
Wrong card parameter setting
Supply voltage under
Electric mains trouble
170V.
Faulty mains frequency Electric mains trouble
Incorrect system water
Pressure too low
pressure
Sensor damaged
Probe damaged or wiring shorted
External probe fault
Probe disconnected after activating the
sliding temperature
Incorrect system water
Pressure too high
pressure
Sensor positioning
Delivery sensor not inserted in boiler shell
Heating sensor fault
Sensor damaged
System water pressure
Wiring disconnected
sensor fault
Cure
Replace
Replace
Replace
Refill with fuel or suck the water
Open
Clean
Prime and find the cause of unprim-
ing
Adjust or clean them
Replace
Replace
Replace
Replace
Replace and protect
Check
Replace
Correct the connection
Replace
Clean the photoresistance
Replace the photoresistance
Eliminate light source
Check the correct positioning and
operation of the heating sensor
Check the circulating pump
Vent the system
Check the card parameter and mod-
ify it if necessary
Check the preheater
Check the wiring
Check the card parameter and mod-
ify it if necessary
Check the wiring or replace the sen-
sor
Check the card parameter and mod-
ify it if necessary
Check the card parameter and mod-
ify it if necessary
Check the wiring or replace the sen-
sor
Check the card parameter and mod-
ify it if necessary
Check the electrical system
Check the electrical system
Fill the system
Check the sensor
Check the wiring or replace the sen-
sor
Reconnect the external probe or dis-
able the sliding temperature
Check the system
Check the safety valve
Check the expansion tank
Check the correct positioning and
operation of the heating sensor
Replace the sensor
Check the wiring