Safety input and command status (TEST mode)

DISPLAY
POSSIBLE CAUSE
The release handle is open.
(Sb)
The safety STOP contact is open.
Sensing edge COS1 not connect-
ed or incorrectly connected.
Sensing edge COS2 not connect-
ed or incorrectly connected.
Photocell FT1 not connected or
incorrectly connected.
Photocell FT2 not connected or
incorrectly connected.
Both limit switches in open con-
tact state or not connected.
Gate is at gate closed limit switch. If the limit switch state indicated is
Gate open limit switch absent or
not connected.
Gate is at gate closed limit switch. If the limit switch state indicated is
Gate closed limit switch absent or
not connected.
If occurs with no voluntary com-
faulty or one of the buttons may be
incorrectly connected.
If occurs with no voluntary com-
faulty or the timer may be incor-
rectly connected.
N.B. Press TEST button to exit from the TEST Mode.
We recommend troubleshooting safety device and input status errors with "corrective action by software" only.
70
ACTION BY SOFTWARE
-
-
Set the parameter
if not
used or to disable
Set the parameter
if not
used or to disable
Set the parameter
e
if not used or to disable
Set the parameter
e
if not used or to disable
-
meter
.
-
meter
.
-
-
-
-
-
-
PHYSICAL CORRECTIVE ACTION
Close the release handle and turn the
key to the close position.
Check that the release contact is con-
nected correctly.
Install a STOP button (NC) or jumper
the ST contact with the COM contact.
Jumper contact COS1 with contact
COM
Jumper contact COS2 with contact
COM
Jumper contact FT1 with contact COM
if not used or to disable. Check con-
nection referring to relative connection
Jumper contact FT2 with contact COM
if not used or to disable. Check con-
nection referring to relative connection
Check connection of limit switches.
-
-
Check connection of limit switches.
-
-
Check connection of limit switches.
Check PP - COM contacts and connec-
tions to buttons.
Check CH - COM contacts and connec-
tions to buttons.
Check AP - COM contacts and connec-
tions to buttons.
Check PED - COM contacts and connec-
tions to buttons.
Check ORO - COM contacts. Contact
must not be jumpered if not used.