Safety Input And Command Status (Test Mode) - Roger Technology H70/200AC Instrucciones Y Advertencias Para El Instalador

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 141
14

Safety input and command status (TEST mode)

With no currently active commands, press the TEST button and check the following:
DISPLAY POSSIBLE CAUSE
The safety STOP contact is open.
Sensing edge COS1 not connected or
incorrectly connected.
Sensing edge COS2 not connected or
incorrectly connected.
Photocell FT1 not connected or incor-
rectly connected.
Photocell FT2 not connected or incor-
rectly connected.
At least 3 limit switches in open contact
state or not connected.
Both gate leaves at open limit switch.
Open limit switch not connected.
Both gate leaves at closed limit switch.
Closed limit switch not connected.
LEAF 1 limit switches not connected or in-
correctly connected.
LEAF 2 limit switches not connected or in-
correctly connected.
LEAF 1 open limit switch not connected
or incorrectly connected.
Or LEAF 1 is open.
LEAF 1 closed limit switch not con-
nected or incorrectly connected.
Or LEAF 1 is closed.
LEAF 2 open limit switch not connected
or incorrectly connected.
Or LEAF 2 is open.
LEAF 2 closed limit switch not con-
nected.
Or LEAF 2 is closed.
If occurs with no voluntary command, the
contact (N.O.) may be faulty or one of the
buttons may be incorrectly connected.
If occurs with no voluntary command, the
contact (N.O.) may be faulty or the timer
may be incorrectly connected.
N.B.: Press TEST button to exit from the TEST Mode.
We recommend troubleshooting safety device and input status errors with "corrective action by software" only.
74
ACTION BY SOFTWARE
-
Set the parameter
if not used
or to disable.
Set the parameter
if not used or
to disable.
Set the parameter
e
used or to disable.
Set the parameter
e
used or to disable.
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
PHYSICAL CORRECTIVE ACTION
Install a STOP button (NC) or jumper the
ST contact with the COM contact.
Jumper contact COS1 with contact
COM, if not used or to disable
Jumper contact COS2 with contact COM,
if not used or to disable.
Jumper contact FT1 with contact COM, if
if not
not used or to disable. Check connection
referring to relative connection diagram
if not
Jumper contact FT2 with contact COM, if
not used or to disable. Check connection
referring to relative connection diagram
Check connection of limit switches.
-
Check connection of limit switches.
-
Check connection of limit switches.
Check connection of limit switches.
Check connection of limit switches.
Check connection of limit switches.
Check connection of limit switches.
Check connection of limit switches.
Check connection of limit switches.
Check PP - COM contacts and connec-
tions to buttons.
Check CH - COM contacts and connec-
tions to buttons.
Check AP - COM contacts and connec-
tions to buttons.
Check PED - COM contacts and connec-
tions to buttons.
Check ORO - COM contacts. Contact
must not be jumpered if not used.