6 Mounting
Maschinenfabrik Reinhausen GmbH 2021
You can connect the following types of analog sensors:
▪ 0/4...20 mA
▪ 0 to 10 V
▪ PT100/PT1000 (2-wire, 3-wire, 4-wire) indirectly via measuring transducer
In order to correctly record the analog signals, you must place the cable
shielding on the grounding bar. The cable shielding should only be removed
just prior to connecting to ensure that the section with unshielded cables is
kept as short as possible. The shielding must be connected with shielding
clips.
Block diagram and wiring versions
AI 4
Connection of a 2-
conductor measuring
transducer with current
Figure 33: Block diagram for analog inputs
1. Lead the wires into the connector and fasten them using a screwdriver.
2. Insert the plug into the respective slot in accordance with the connection
diagram and screw into place.
6.4.8 Wiring digital inputs DI
If you use digital inputs, these have to be supplied with an auxiliary voltage
of 110 V DC.
1. Feed the wires into the terminal of the DI 16-110V plug in accordance with
the connection diagram [►Section 10.14, Page 67] and fasten them us-
ing a screwdriver.
2. Plug the connector into the respective slot and screw it into place.
Auxiliary supply voltage for digital inputs
1. Feed the wires into the terminals X8:2 and X8:1 of the X8 plug in accor-
dance with the connection diagram [►Section 10.14, Page 67] and fas-
ten them using a screwdriver.
2. Plug the connector into the respective slot and screw it into place.
7820658/01 EN
CAN bus
Controller
Reinforced insulation
D
D
A
A
Connection of a 4-
conductor measuring
conductor measuring
transducer with voltage
transducer with current
output