Tap Position Capture / Resistor Contact Series; Ambient Conditions; Standards And Directives - MR TAPCON 230 Instructions De Montage

Ocultar thumbs Ver también para TAPCON 230:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

10 Technical data

10.11 Tap position capture / resistor contact series

10.12 Ambient conditions

10.13 Standards and directives

Maschinenfabrik Reinhausen GmbH 2021
Electrical isolation
Electrical isolation
Tap position capture
Operating temperature
Storage temperature
Relative humidity
Maximum installation alti-
tude
Minimum clearance to
other devices / control
cabinet
Table 31: Permissible ambient conditions
Electromagnetic compatibility
Electrical safety
Climatic ambient conditions
Degree of protection
Degree of protection with accessory con-
trol cabinet
7820658/01 EN
Test voltage power-frequency withstand volt-
age: 500 V
; 50 Hz; 1 min
eff
Test voltage power-frequency withstand volt-
age: 500 V
; 50 Hz; 1 min
eff
35 tap positions, 2,000 ohms
-25...+70°C
-30...+85°C (with battery)
5...95%, non-condensing
3,000 m above mean sea level
Above/below: 88.9 mm (3.5 in; equivalent to 2RU), be-
hind 30 mm (1.2 in)
IEC 61000-6-5, IEC 61000-6-2,
IEC 61000-6-4 and EN 60255-26
IEC 61010-1
IEC 60068-2-1 (-25°C; 96 h) cold
IEC 60068-2-2 (+70°C; 96 h) dry heat
IEC 60068-2-78 (+40°C / 93% rH, 96 h)
moist heat, constant
IEC 60068-2-30 (+55°C, 6 cycles 12 +
12 hours) moist heat, cyclical
EN 60529
Front: IP54
Rear: IP20
EN 60529
IP66
®