6 Mounting
DANGER
WARNING
NOTICE
Maschinenfabrik Reinhausen GmbH 2021
6 Mounting
Electric shock!
Risk of fatal injury due to electrical voltage. Always observe the following
safety regulations when working in or on electrical equipment.
► Disconnect the equipment.
► Lock the equipment to prevent an unintentional restart.
► Make sure all poles are de-energized.
► Ground and short-circuit.
► Cover or cordon off adjacent energized parts.
Electric shock!
Dangerous high voltages may occur when a current transformer is operated
with an open secondary circuit. This can lead to death, injuries and property
damage.
► Never operate a current transformer with an open secondary circuit;
short-circuit the current transformer to prevent this.
► Observe the information in the current transformer operating instructions.
Damage to the device!
Electrostatic discharge may cause damage to the device.
► Take precautionary measures to prevent the build-up of electrostatic
charges on work surfaces and personnel.
6.1 Preparation
The following tools are needed for mounting:
Depending on the installation site and mounting version, you may need ad-
ditional tools and corresponding attachment material, such as screws, nuts
and washers which are not included in the scope of delivery.
▪ Depending on mounting version:
– Electric jigsaw for flush panel mounting.
– Drill for wall mounting (wall mounting with housing).
▪ Screwdriver for connecting the signal lines and supply lines.
7820658/01 EN
®
TAPCON
230
27