Alliance Laundry Systems UW35PV Instalación/Mantenimiento página 31

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

The AC drive provides thermal overload
protection for the drive motor. However, a
separate three-phase circuit breaker or
electrical supply disconnecting device must be
installed for complete electrical overload
protection. This prevents damage to the motor
by disconnecting all legs if one should be lost
accidentally. Check the data plate on the back
of the washer-extractor or consult the
Electrical Specifications chart in this
subsection for circuit breaker requirements.
Do NOT use fuses in place of a circuit
Note:
breaker.
CAUTION
Do not use a phase adder on any variable-
speed machine.
The washer-extractor should be connected to
an individual branch circuit not shared with
lighting or other equipment.
The connection should be shielded in a liquid-
tight or approved flexible conduit with proper
conductors of correct size installed in
accordance with the National Electric Code or
other applicable codes. The connection must
be made by a qualified electrician using the
wiring diagram provided with the washer-
extractor, or according to accepted European
standards for equipment labelled with the CE
mark.
F232084
SW037
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Installation
Use wire sizes indicated in the Electrical
Specifications chart for runs up to 50 feet. Use
next larger size for runs of 50 to 100 feet. Use
2 sizes larger for runs greater than 100 feet.
For personal safety and for proper operation,
the washer-extractor must be grounded in
accordance with state and local codes. If such
codes are not available, grounding must
conform with the National Electric Code,
article 250-95 or accepted European standards
for equipment labelled with the CE mark. The
ground connection must be made to a proven
earth ground, not to conduit or water pipes.
Refer to Figure 10.
Ground Lug: Connect to
proven earth ground.
Connections to
Control Module
(L1)
(L2)
R
S
Black
Blue
Figure 10
Power
Input
Block
(L3)
T
Red
P059IE3A
29

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

Uw80pvUw125pvUw60pvUw100pv

Tabla de contenido