Line
Function
95
Function of Q1 output pump
1 Installation pump (or no pump)
2 Main pump (heating only)
3 Main pump (heating and D.H.W.)
4 D.H.W. circulation pump
5 H1 pump
97
Use of B70/B4 input (feeler)
1 Cascade return temperature (B70)
2 Additional accumulation temperature (B4)
100
Parallel shift of heating curve
101
Influence of room temperature
0 Non active
1 Active
102
Room temperature differential (SDR)
--.- Non active
0,5...4,0 Active
103
Minimum limit of delivery temperature (Tvmin)
Tvmax line 104
104
Maximum limit of delivery temperature (Tvmax)
Tvmin line 103
105
Type of building
0 heavy
1 light
106
Self-adjustment of climatic curve
0 Non active
1 Active
107
Maximum spark advance of ignition optimum control
108
Max. spark advance of blowing-out optimum control
120
D.H.W. reduced setpoint value (TBWR)
TBWw line 13
121
D.H.W. program
0=24h/24h
1= According to the heating programs with advance timing
2= According to the D.H.W. program (timer)
122
Timer for circulation pump
0 According to the heating program
1 According to the D.H.W. timer
123
D.H.W. attribution
0 Local user only
1 All users of the same segment
2 All users of the system
124
D.H.W. preparation
0 One time a day with a 2,5 hour advance
1 Every time it is necessary with 1 hour advance
125
Type of D.H.W. requirement
0 Temperature feeler
126
Over-raising of boiler temperature
due to requirement of D.H.W. production
127
D.H.W. priority
0 Absolute
1 Shifting
2 Parallel
3 Mixed (pump: absolute; mix.valve: shifting)
129
Heat requirement with reduced D.H.W. setpoint
0 No (applications with additional accumulation)
1 Yes
130
Automatic reversal of the cascade boilers
--- Fixed sequence
10...990 Interval between reversals
131
Cut-out of automatic reversal
of the cascade boilers
0 No one
2 Last boiler
Field
1...5
1..2
–4,5 +4,5
0/1
--.-/0,5...4,0
8...Tvmax
Tvmin...95
0/1
0/1
00:00...06:00
00:00...06:00
8...TBWw
0...2
0... 1
0...2
0... 1
0... 1
1 Thermostat
0...30
0...3
0/1
---/10...990
0...3
1 First boiler
3 First and last boiler
U/M
Resolution
Default value
1
K (°C)
0,5
1
K(°C)
0,5
°C
1
°C
1
1
1
hh:mm
10 min
hh:mm
10 min
°C
1
1
1
1
1
1
K (°C)
1
1
1
1
1
–/h
10
1
Personal value
1
1
0,0
1
--,-
8
80
1
1
00:00
00:00
40
1
1
2
1
0
16
1
1
500
0
55