ZONE 3: RVA 46.531: Pump and room unit
(Please refer to the RVA46.531 manual)
Installation ID
– Setting mode = USER
(please refer to the "Parameter setting levels" paragraph)
Par
Description
17*
Heating curve slope
* According to the installation type
– Setting mode = INSTALLER
(please refer to the "Parameter setting levels" paragraph)
Par
Description
67
Room temp. operating differential
69* Max. limit of delivery temp. setpoint
85
LPB-equipment address
87
Operation with timer
* According to the installation type. In pump-operated circuits, the room unit is
needed to avoid excess temperatures.
ZONE 4: RVA 46.531: Mixing valve, pump, zone feeler, excess
temperature thermostat and room unit (floor installation)
(Please refer to the RVA46.531 manual)
Installation ID
– Setting mode = USER
(please refer to the "Parameter setting levels" paragraph)
Par
Description
17*
Heating curve slope
* According to the installation type
– Setting mode = INSTALLER
(please refer to the "Parameter setting levels" paragraph)
Par
Description
69* Max. limit of delivery temp. setpoint
85
LPB-equipment address
87
Operation with timer
* According to the installation type.
NOTE 1: If there are more than three zones, each controlled by a
RVA 46.531 central unit, the parameter setting is analogous and
you go on with the LPB equipment addresses in mounting progres-
sion. If you 'd like to install several external temperature feelers (for
apartments more or less exposed to sunlight), those must be con-
nected to the RVA 46.531 central units and you must take into con-
sideration the fact that the signal propagates towards the equip-
ment address with the highest number.
NOTE 2: The thermostat for excess temperature has the purpose of
stopping the production of heat in case the water temperature gets
too high and damages the floor. We recommend setting at 45°C.
NOTE 3: If there are only 2 zones controlled by a RVA 46.531 regula-
tor, the first RVA 46.531 regulator will have 2 as its LPB-equipment
address (parameter 85) and the second one will have 3 as its LPB-
equipment address.
3.5.4
Verifying the correct recognizing
To make sure the regulator has correctly recognized the installation
on the basis of the input parameters, display the "Installatore" para-
meter on line 53 of the regulators. For RVA 47.320, installation # 35
must be displayed; for the first RVA 46.531 (Zone 2), installation #
11; for the second RVA 46.531 (Zone 3), installation # 12 and finally
48
Default values
Setup
15
15
Default values
Setup
–.––
1
80
70
0
4
0
2
Default values
Setup
15
7,5
Default values
Setup
80
37
0
5
0
2
for the third RVA 46.531 (Zone 4), installation # 11.
Par Description
Zone 1
53
Type of installation
35
4
FUNCTION TESTS
Once the installation of the regulator and all the electrical connec-
tions are done and ready, it is better to check the configuration by
means of the input and output tests, which allow quick identification
of malfunctions and failures.
51
Output test
With this test, all outputs can be checked before the setting at work
of the boiler.
Buttons
Explanation
PUSH BOTH THE LINE SELECTION BUTTONS FOR
1
AT LEAST 3 SECONDS.
THIS WILL LEAD YOU INTO THE OUTPUT TEST
PUSH THE +/– BUTTONS REPEATEDLY
2
TO MOVE ONE STEP FORWARD
ALL OUTPUTS PERFORM THEIR
TEST STEP 0
TEST STEP 1
TEST STEP 2
TEST STEP 3
TO QUIT THE PROGRAMMING MODE AND THE
OUTPUT TEST, PUSH ONE OF THE WORKING
MODE BUTTONS.
3
If no button is pushed for 8 minutes,
the control device will return automatically
to the last selected working mode.
52
Input test
This is also called "feeler test" and it is used to check the wiring and
the configuration of all the sensors.
Buttons
Explanation
PUSH BOTH THE LINE SELECTION BUTTONS FOR
1
AT LEAST 3 SECONDS. THIS WILL
LEAD YOU INTO THE PROGRAMMING MODE.
PUSH THE "SU" SELECTION BUTTON UNTIL
2
YOU REACH LINE 52. THIS WILL
LEAD YOU INTO THE INPUT TEST.
TEST STEP 0
TEST STEP 1
TEST STEP 2
3
TEST STEP 3
TEST STEP 4
TEST STEP 5
TO QUIT THE PROGRAMMING MODE AND THE
INPUT TEST, PUSH ONE OF THE WORKING
MODE BUTTONS.
4
If no button is pushed for 8 minutes,
the control device will return automatically
to the last selected working mode.
Zone 2
Zone 3
Zone 4
11
12
11
Line
SWITCHING FUNCTIONS
ACCORDING TO THE
CONTROL MODE
ALL OUTPUTS
OFF/DISABLED
D.H.W. HEAD PUMP
IS ACTIVATED (Q3)
PUMP IS ACTIVATED (Q1)
Line
CASCADE RETURN
TEMPERATURE (B70 / B4)
D.H.W. TEMPERATURE (B3)
CASCADE DELIVERY
TEMPERATURE (B10)
EXTERNAL TEMPERATURE B9
ROOM TEMPERATURE A6
FUNCTION SET
AT LINE 170 (H1)
51
51
51
52
52