3.2.3
Parameter setting
For the regulator to be able to recognize this installation you need to
set the following parameters as shown in the table.
Installation ID
– Setting mode = INSTALLER
(please refer to the "Parameter setting levels" paragraph)
Par
Description
140
LPB address
148
Timer
170
H1 input management
173
Function of contact connected to H1
NOTE: In the case of non-condensation boilers, the return tempera-
ture must be raised in order to avoid the problems related to the flue
gas condensate. To do so, the OEM 22 parameter must be modified.
– Setting mode = MANUFACTURER
(please refer to the "Parameter setting levels" paragraph)
Par
Description
22
Min. limit of cascade return temperature
3.2.4
Verifying the correct recognizing
To make sure the regulator has correctly recognized the installation on
the basis of the input parameters, display the "Installer" parameter on
line 53.
Installation n° 34 must appear (n° 36 in the case of DEWY EQUIPE).
3.3. 1
Sequence management of up to 4 boilers for heating with a combined boiler
Hydraulic circuit
BOILER 1
CALDAIA 1
(combinata)
(combined)
KEY
SI
Hydraulic separator
SM
Cascade delivery temperature feeler (QAD21)
SR
Cascade return temperature feeler (QAD21)
Default
Setup RVA :
values
Master
Slave
1
1
2
3
3
1
0
1
-
1
0
-
Default values
Setup
8°C
20°C
PPS BUS
BOILER 2
BOILER 3
CALDAIA 2
CALDAIA 3
3.3
HEATING INSTALLATION
WITH COMBINED BOILER (I2)
Characteristics in outline:
– Cascade management of up to 4 boilers
– Continuous power modulation of the entire cascade with automa-
tic management of the switching on/off of the single modules.
– Self-adjusting to the heat requirements.
– Automatic turnover of the boiler sequence.
– Automatic Summer/Winter switching.
– Climate adjustment with external feeler.
– The boilers are activated only by a signal from the room thermostat.
– The installation pump is activated only by a signal from the room
thermostat.
– Daily heating program option.
– The settings of the combined boiler can be made directly from the
"RVA 47.320" regulator.
– On/Off switching of sanitary hot water production through a but-
ton on the regulator.
– 7-day program option for sanitary hot water.
– Automatic distribution of the heating power onto the remaining
boilers when one boiler is engaged in the hot water production.
The components of the kit to be used are:
Code
Description
RVA 47.320 Central unit for controlling boiler cascade
QAC31
External temperature feeler
QAD21
Feelers for delivery/return temperature of cascade
––
"Albatros" jumper for configuration
––
4 stickers for boiler numbering (kit)
––
4 configuration resistors (kit)
SE
RVA
47.320
BOILER 4
CALDAIA 4
SR
SE
External temperature feeler (QAC31)
PI
Installation pump
TA
Room thermostat
C
ALBATROS RVA47.320 regulator
4 boilers 6 boilers
1
1
2
4
1
1
TA
C
SM
PI
M
SI
R
ES
ENG
FR
BE
Quantity up to
2
1
2
6
2
2
37