ACS 500
..6.
Program description
.
Fill internal cylinder
i
Before filling, refer to section 4.2 "Filling the
internal refrigerant cylinder".
Program sequence for topping up
!
Only ever fill the refrigerant cylinder to a
maximum of 70% (approx. 6.5 kg).
The subsequent program sequence is descri-
bed using the following example values:
Filling weight of internal refrigerant cylin-
der: e.g. 2760 g.
Filling weight for topping up: 3300 g.
Filling weight of internal refrigerant cylin-
der after topping up: 6460 g = 2760 g +
3300 g + 400 g (residual quantity in hose
lines).
Robert Bosch GmbH
Caution - risk of frostbite!
If refrigerant escapes, there is a risk of frost-
bite to the hands and body.
Wear protective goggles.
Wear protective gloves.
1.
In the main menu, select the "Fill internal
cylinder" option and follow the instruc-
tions in the program.
2.
Connect the red quick release coupling
(Fig. 1; 8) on the ACS 500 to the connec-
ting adapter on the external refrigerant
cylinder.
3.
Open the shutoff valve on the red quick
release coupling (turn clockwise).
4.
Open shutoff valve on external refrigerant
cylinder.
The current internal pressure of the
external refrigerant cylinder is displa-
yed on the high pressure manometer
(HP).
5.
Open the high pressure valve (HP) on the
ACS 500.
6.
Press the V key.
The maximum weight for filling is dis-
played.
7.
When the maximum weight is displayed,
enter the filling weight as shown in the
example (3300 g).
8.
Press the V key.
Filling of the internal refrigerant cy-
linder begins. Follow the instructions
in the program.
"
After filling, the "Resources" option in the
main menu shows the current weight of
the internal refrigerant cylinder.
1 689 979 953 (2006-10-19)
en