Safety ribbon 1 input
This menu allows enabling the input for type 1 safety ribbon, that is to
say, fixed ribbons (see paragraph "Installation").
no
input disabled (ignored by the control unit).
AP
Input enabled during the opening and disabled during the
closure
APCH
Input enabled in opening and closure
Safety ribbon 2 input
This menu allows enabling the input for type 2 safety ribbon, that is to
say mobile ribbons (see paragraph "Installation").
no
input disabled (ignored by the control unit).
No jumper with the common is required.
Ch
Input enabled during closure and disabled during opening
APCH
Input enabled in opening and closure
Test of the safety edges
This menu allows setting the method of control of the safety edges
working.
no
Test disabled
Foto
Test enabled for optical safety edges
rESi
Test enabled for conductive rubber safety edges
WARNING: V2 suggests to keep activated the test of the
photocells in order to grant a higher safety of the system.
End of Stroke Inputs
The CITY2+ controller permits the connection of 4 normally closed (NC)
limit switches that are activated by the gates movement and indicate to
the controller if the gate has reached the completely open or closed
position.
Si
end of stroke inputs are enabled
no
end of stroke inputs are disabled
46