15. Electric connecti on
DANGER! Live parts. Electrocuti on.
REMOVE THE ELECTRIC POWER SUPPLY BEFORE ANY OPERATION!
ensure that the casing does not come into contact with the electrical panel
Provide a suitable grounding system!
i
The systems must be set up in accordance to the norms that regulate manufacture, installa-
ti on, use, and maintenance foreseen by the norms in force in the country where the refrigera-
ti on system is installed.
To ensure normal operati on, the maximum variati on of the voltage must range between +/-
6% of the nominal value.
Liability
Power
power supply
Automati c
safety switches
4 0
Code
04 711065
04 230600
029 4 0652
0204 7000
Customer
provide a power line to the cabinet connecti on point.
Installer
provide the anchoring devices for all the wires in input and out-
put to/from the cabinet.
ARNEG
ARNEG S.p.A. denies all liability with respect to the user or third
parti es for:
- damages caused by failures or malfuncti on of the systems
installed upstream of the cabinet
- damages to the cabinet due to causes arising directly from
malfuncti on of the electrical system
• the supply lines of the electric energy should meet the requirements of power
consumpti on of the cabinet chap.9.
• check that the power line:
- has wires with suitable cross secti on
- is protected against over-current, overload and dispersions toward earth in
accordance with the rules in force
• protect the upstream cabinets with omnipolar circuit breakers with suitable
characteristi cs that will also functi on as master switches to secti on off the line
• instruct the operator on the positi on of the switches to be reached quickly in
case of EMERGENCY
DANGER! Live parts. Short circuit. Electrocuti on
The automati c magneto-thermal switches must be such that they do
not open the circuit on the neutral, without simultaneously opening
on the phases and, in any case, must allow complete disconnecti on in
conditi ons of category III overvoltage
05060171 00 13-02-2018