5. Confi rmation of parts attached
•
This unit includes the following parts. Please check.
•
For usage methods, refer to item 10.2.
1 Connecting pipe
ID ø25.4, ID ø22.2
<Low-pressure side>
<High-pressure side>
Model
P250
EP250
P300
EP300
P350
P400
6. Space required around unit
1 In case of single installation
•
Secure enough space around the unit as shown in the fi gure on page 2.
[Fig. 6.0.1] (P.2)
<A> Top view
<B> Side view
<C> When there is little space up to an obstruction
Front
A
B
Back
C
D
(1) If the distance is 300 mm or more between the rear side and the wall
(2) If the distance is 100 mm or more between the rear side and the wall
(3) If the wall height (H) of the front, rear or side exceeds the wall height
restriction
•
When the height of the walls on the front, back or on the sides <H> exceeds
the wall height limit as defi ned here, add the height that exceeds the height
limit <h> to the fi gures that are marked with an asterisk.
7. Lifting method
[Fig. 7.0.1] (P.2)
•
Use suspension ropes that will withstand the weight of the unit.
•
When moving the unit, use a 4-point suspension, and avoid giving impacts
to the unit (Do not use 2-point suspension).
•
Place protective pads on the unit where it comes in contact with the ropes to
protect the unit from being scratched.
•
Set the angle of roping at 40° or less.
•
Use 2 ropes that are each longer than 8 meters.
8. Installation of unit
8.1. Installation
[Fig. 8.1.1] (P.3)
<A> Without detachable leg
M10 anchor bolt procured at the site.
A
Fixing bracket for the hole-in anchor
C
bolt (3 locations to fi x with screws).
•
Fix unit tightly with bolts so that unit will not fall down due to earthquakes or
strong winds.
•
Use concrete or an angle bracket for the foundation of unit.
•
Vibration may be transmitted to the installation section and noise and
vibration may be generated from the fl oor and walls, depending on the
installation conditions. Therefore, provide ample vibrationproofi ng (cushion
pads, cushion frame, etc.).
•
Be sure that the corners are fi rmly seated. If the corners are not fi rmly
seated, the installation feet may be bent.
•
When using cushion pads, be sure that the full width of the unit is covered.
•
The projecting length of the anchor bolt should be less than 30 mm.
•
Hole-in anchor bolts are not compatible with this product. However, if fi xing
brackets are mounted on the 4 locations of the unit attachment part, hole-in
anchor bolts can be used.
2 Connecting pipe
ID ø25.4, OD ø19.05
<High-pressure side>
1 pc.
–
1 pc.
1 pc.
1 pc.
–
1 pc.
1 pc.
–
1 pc.
1 pc.
–
Unit height
Air outlet guide (Procured at the site)
<B> With detachable leg
Corner is not seated.
B
Detachable leg
D
3 Connecting pipe
4 Connecting elbow
ID ø25.4, ID ø28.58
ID ø19.05, OD ø19.05
<Low-pressure side>
<High-pressure side>
–
–
–
1 pc.
–
–
–
1 pc.
1 pc.
1 pc.
1 pc.
–
<Wall height limit> Front: Up to the unit height
Back: Up to 500 mm from the unit bottom
Side: Up to the unit height
(4) If there are obstacles at the upper part of the unit
2 In case of collective installation
[Fig. 6.0.2] (P.2)
A Front
C Wall height (H)
•
When multiple units are installed adjacent to each other, secure enough
space to allow for air circulation and walkway between groups of units as
shown in the fi gures on page 2.
•
At least two sides must be left open.
•
As with the single installation, add the height that exceeds the height limit
<h> to the fi gures that are marked with an asterisk.
•
Place protective padding at the corners of the product to protect the product
from scratches or dents that might be caused by the rope.
Caution:
Be very careful when carrying/moving the product.
- When installing the outdoor unit, suspend the unit at the specifi ed location of
the unit base. Stabilize as necessary so that it does not move to the side and
support it at 4 points. If the unit is installed or suspended with 3-point support,
the unit may become unstable and fall.
[Fig. 8.1.2]
A Screws
•
The detachable leg can be removed at the site.
•
Detaching the detachable leg
Loosen the three screws to detach the detachable leg (Two each in the front
and back).
If the base leg fi nish is damaged when detaching, be sure to repair at the
site.
Warning:
•
Be sure to install unit in a place strong enough to withstand its weight.
Any lack of strength may cause unit to fall down, resulting in a
personal injury.
•
Have installation work in order to protect against strong winds and
earthquakes.
Any installation defi ciency may cause unit to fall down, resulting in a
personal injury.
When building the foundation, give full attention to the fl oor strength, drain water
disposal <during operation, drain water fl ows out of the unit>, and piping and
wiring routes.
Precautions when routing the pipes and wires below the unit (Without
detachable leg)
When routing the pipes and wires below the unit, be sure that the foundation and
base work do not block the base through-holes. Also make sure the foundation
is at least 100 mm high so that the piping can pass under the unit.
B Must be open
13