Installation
3.7.3
Metal pipe with loose flanges
Fig. 17
3.7.4
Non-metallic pipes or pipes with insulating liner
Fig. 18
3.7.5
Flowmeter sensor in stainless steel design model SE21
Ground the stainless steel model as shown in the figure. The measuring fluid is grounded via
the adapter (1) and an additional ground is not required.
Fig. 19
3.7.6
Ground for devices with hard rubber lining
For devices with meter sizes DN 125 and larger, the liner contains a conductive element. This
element grounds the measuring agent.
3.7.7
Ground for devices with protective plates
The protective plates are used to protect the edges of the liner in the measuring tube, e.g., for
abrasive fluids. In addition, they function as a grounding plate.
•
For plastic or pipes with insulating lining, electrically connect the protective plate in the same
manner as a grounding plate.
3.7.8
Ground with conductive PTFE grounding plate
For devices with a meter size between DN 10 ... 150, grounding plates made of conductive
PTFE are available. These are installed similar to conventional grounding plates.
16 - EN
2
1
3
Flange design
1
2
3
Flange design
1
FSM4000
Wafer design
Wafer design
G00531
G00532
G00533
D184B141U03