Follow the instructions below to connect the machine to the electrical power supply system:
•
Connect the pump to an external
line switch whose distance between
contacts must be at least 3mm
•
The pump must have an earth
connection and must be protected
against indirect contacts in
accordance with local regulations
•
If an automatic differential circuit-
breaker is present on the pump' s power
supply, this must fit for the application
and in any case of type B. When
NOTE
Before switching on or after a long period without power, the display may flash; this indicates the internal clock must be
regulated (see chpt. 5.3.1).
3.6 CONNECTING THE PRESSURE UNIT TO THE POWER SUPPLY
DANGER
Check to ensure that all connections are free from electricity.
DANGER
Always disconnect the electrical power supply cable before working on electrical or mechanical parts in the pressure unit.
DANGER
After disconnecting the power supply, wait until the led LINE goes off (approximately 2 minutes) so that the capacitors can
unload, before working on the CPS.
ATTENTION
Perform the electrical connections in compliance with local standards in force.
ATTENTION
The installer is responsible for checking that the electrical power supply system is equipped with an efficient earthing
system in accordance with current regulations.
choosing the device, it is important
to consider the discharge of all the
electric equipments in the system
•
Check that voltage is 3~380-500 Vac,
50/60Hz
•
Screw the male connector that is
present on the cable to the female
connector of the CPS
•
Connect the main supply to clamps 1,
2, 3 and
of the F-connector not
been used yet
•
Connect the F-connector to the
M-connector present on the CPS
•
In specific cases, some additional
components may be required
(for example filters etc...) to limit
electromagnetic interference
EN