Installation
8.1
Spacing Allowances and Unit Dimensions
See fig. 3, page 4:
I
NOTE
The blower is rotatable by 270 degrees, to ease installation and improve air
flow.
Space allowances (fig. 3, page 4)
The following space allowances should be considered when mounting the unit:
•
Allow a minimum of 152 mm clearance around the unit in the area of the sea-
water and condensate drain piping.
•
Allow a minimum of 76 mm of air space in front of the evaporator coil for the
return-air intake if it is adjacent to a bulkhead.
•
For flexible ducting connection and for clearance needed behind the supply-
air grille add the following values to get the total clearance distance:
– 51 mm for the duct ring
– 25 mm for the duct bend radius and
– diameter of the ducting.
•
Allocate enough space for installation and serviceability.
Unit dimensions
Unit Capacity
Minimum duct diameter (mm)
Minimum duct area (cm
Minimum distance return grill (cm
Minimum distance supply grill (cm
18
2
)
2
)
2
)
MCS T6, MCS T12, MCS T16
6 T
12 T
102
152
81
183
413
839
206
452
16 T
152
183
1032
516
EN