Slip Compensation - Parker AC30 Serie Manual Del Producto

Ocultar thumbs Ver también para AC30 Serie:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

D-176
Parameter Reference

Slip Compensation

Parameters::Motor Control::Slip Compensation
Designed for VOLTS/Hz motor Control Mode.
The slip compensation function allows the Drive to maintain motor speed in the presence of increased load.
Parameter Name
No.
Slip Compensatn Enable
0354
Enable/Disable slip compensation
SLP Motoring Limit
0356
Maximum compensated speed in motor control
SLP Regen Limit
0357
Maximum compensated speed in regen mode
Functional Description
Based on the rated speed, the no load speed and the rated load of the motor, the Slip Compensation feature adjusts the demand frequency to
compensate for any speed reduction resulting from the load.
Path
Parameters::Motor Control::Slip
Compensation
Parameters::Motor Control::Slip
Compensation
Parameters::Motor Control::Slip
Compensation
Default
Range
FALSE
150
0 to 600
150
0 to 600
Units
Writable
ALWAYS
RPM
ALWAYS
ALWAYS
RPM