Parker AC30 Serie Manual Del Producto página 315

Ocultar thumbs Ver también para AC30 Serie:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Parameter Name
No.
ATN PMAC Test Disable
1388
This is only valid for Permanent magnet motor control
Allows selected tests to be disabled (default all tests are carried out).
Each test can be individually disabled by setting to TRUE.
Bitfield Value : Test
Autotune Ramp Time
0274
Sets the ramp up time to motor base speed during autotune.
ATN PMAC Ls Test Freq
1405
This is only valid for Permanent magnet motor control
Set up the test frequency for the leakage inductance autotune of the permanent magnet motor control0255 Autotune Ramp Time
Max Spd when Autotuned
1459
This parameter records the value of the "100% speed in rpm" parameter at the time the autotune was carried out.
"100% speed in rpm" determines the max speed at which the motor can be commanded to run. When the autotune is carried out, it
can only measure the motor characteristics up to this speed. Beyond this speed, the motor characteristics are filled in according to the
best possible estimate, but are not necessarily accurate.
If at a later date the "100% speed in rpm" parameter is increased, then that will allow the motor to run in the region where the motor
characteristics have been estimated, not measured. The further into this region the motor is allowed to run, the less accurate will be
the motor characteristics and hence the control.
The user is allowed to increase "100% speed in rpm" up to 2 times the value stored in "Max Spd when Autotuned". Beyond this it is
considered that the resulting control inaccuracy may be unacceptable. In this case, an error will be generated. If the user wishes to
run the motor more than 2 times the value at which it was autotuned, then he must carry out a new autotune at the higher speed.
AC30 series Variable Speed Drive
Path
Setup::Motor Control::Autotune
Parameters::Motor Control::Autotune
Same as PNO 255
Same as PNO 1388
Parameters::Motor Control::Autotune
Parameter Reference
Default
Range
0:Stator Resistance
0000
1:Leakage Inductance
2:KE Constant
10.000
1.000 to 1000.000
100.0
0.0 to 500.0
x.
-1 to 100000
D-23
Units
Writable
STOPPED
s
STOPPED
Hz
STOPPED
NEVER
RPM
Tabla de contenido
loading

Este manual también es adecuado para:

Ac30pAc30d

Tabla de contenido