Skip Frequencies - Parker AC30 Serie Manual Del Producto

Ocultar thumbs Ver también para AC30 Serie:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

D-172
Parameter Reference

Skip Frequencies

Setup::Application::Skip Frequencies
Function availability depends on macro selected.
This function is used to prevent the Drive operating at frequencies that cause mechanical resonance in the load.
Parameter Name
No.
Skip Band 1
1908
The width of skip band 1 in Hz.
Skip Frequency 1
1909
The centre frequency of skip band 1 in Hz.
Skip Band 2
1910
The width of skip band 2 in Hz.
Skip Frequency 2
1911
The centre frequency of skip band 2 in Hz.
Skip Band 3
1912
The width of skip band 3 in Hz.
Skip Frequency 3
1913
The centre frequency of skip band 3 in Hz.
Skip Band 4
1914
The width of skip band 4 in Hz.
Path
Setup::Application::Skip Frequencies
Setup::Application::Skip Frequencies
Setup::Application::Skip Frequencies
Setup::Application::Skip Frequencies
Setup::Application::Skip Frequencies
Setup::Application::Skip Frequencies
Setup::Application::Skip Frequencies
Default
Range
0.0
0.0 to 1000.0
0.0
0.0 to 1000.0
0.0
0.0 to 1000.0
0.0
0.0 to 1000.0
0.0
0.0 to 1000.0
0.0
0.0 to 1000.0
0.0
0.0 to 1000.0
Units
Writable
Hz
ALWAYS
Hz
ALWAYS
Hz
ALWAYS
Hz
ALWAYS
Hz
ALWAYS
Hz
ALWAYS
Hz
ALWAYS
AC30 series Variable Speed Drive
Tabla de contenido