Vertical kit with aluminium tile Ø 80/125. Kit
CZ
assembly (Fig. 1-23): install the concentric flange
(2) on the central hole of the boiler inserting the
gasket (1) and tighten using the screws in the
kit. Fit the male end (smooth) of the adapter (3)
SI
into the female end of the concentric flange (2).
Imitation aluminium tile installation. Replace
the tile with the aluminium sheet (5), shaping
it to ensure that rainwater runs off. Position
HU
the fixed half-shell (7) on the aluminium tile
and insert the intake-exhaust pipe (6). Fit the Ø
80/125 concentric terminal pipe with the male
end (6) (smooth) to the female end of the adapter
RU
(3) (with lip gasket) up to the stop; making sure
that the wall sealing plate has been fitted, this
will ensure sealing and joining of the elements
making up the kit.
RO
• Coupling extension pipes and concentric
elbows. To install push-fitting extensions with
other elements of the flue extraction elements
IE
assembly, proceed as follows: engage the
concentric pipe or elbow with the male side
(smooth) on the female section (with lip seal)
up to the stop on the previously installed ele-
SK
ment. This will ensure sealing and joining of
the elements correctly.
UA
5
4
3
2
1
252
2
3
4
5 6
The kit includes:
N°1 - Gasket (1)
N°1 - Concentric bend Ø 60/100 (2)
N°1 - Adapter Ø 60/100 for Ø 80/125 (3)
N°1 - Int./exhaust concentric terminal
Ø 80/125 (4)
N°1 - Internal white wall sealing plate (5)
N°1 - External grey wall sealing plate (6)
Important: if the exhaust terminal and/or exten-
sion concentric pipe needs shortening, consider
that the internal pipe must always protrude by
5 mm with respect to the external pipe.
This specific terminal enables flue exhaust and
air intake, necessary for combustion, in a verti-
cal direction.
N.B.: The Ø 80/125 vertical kit with aluminium
tile enables installation on terraces and roofs
with a maximum slope of 45% (25°) and the
height between the terminal cap and half-shell
(374 mm) must always be respected.
The vertical kit with this configuration can be
extended up to a maximum of 12,200 mm vertical
rectilinear, with the terminal included (Fig. 1-24).
This configuration corresponds to a resistance
factor of 100. In this case the special extensions
must be requested.
The terminal Ø 60/100 can also be used for
vertical exhaust, in conjunction with concentric
flange code 3.011141 (sold separately). The
height between the terminal cap and half-shell
(374 mm) must always be respected.
The vertical kit with this configuration can
be extended up to a maximum of 4,700 mm
vertical rectilinear, with the terminal included
(Fig. 1-24).
8
The kit includes:
N°1 - Gasket (1)
7
N°1 - Female concentric flange
(2)
N°1 - Adapter Ø 60/100 for
Ø 80/125 (3)
N°1 - Wall sealing plate (4)
N°1 - Aluminium tile (5)
N°1 - Concentric intake-exhaust
6
terminal Ø 80/125 (6)
N°1 - Fixed half-shell (7)
N°1 - Mobile half-shell (8)
C12
C32
Fig. 1-23
Separator kit Ø 80/80. The Ø 80/80 separator
kit, allows separation of the exhaust flues and
air intake pipes according to the diagram shown
in the figure. Combustion products are expelled
from pipe (B). Air is taken in through pipe (A)
for combustion. The intake pipe (A) can be
installed either on the right or left hand side of
the central exhaust pipe (B). Both ducts can be
routed in any direction.
• Kit assembly (Fig. 1-25): install flange (4) on the
central hole of the boiler, fitting gasket (1) and
tighten with the flat-tipped hex screws included
in the kit. Remove the flat flange present in the
lateral hole with respect to the central one (ac-
cording to needs) and replace it with the flange
(3), positioning the gasket (2) already present in
the boiler and tighten using the supplied self-
threading screws. Fit the male end (smooth) to
the bends (5) in the female end of the flanges
(3 and 4). Fit the intake terminal (6) with the
male section (smooth) in the female section of
the bend (5) up to the stop, ensuring that the
internal and external wall sealing plates are fit-
ted. Fit the exhaust pipe (9) with the male end
(smooth) to the female end of the bend (5) up
to the stop; making sure that the internal wall
sealing plate has been fitted. This will ensure
sealing and joining of the elements making up
the kit.
C12
Fig. 1-21
C32
Fig. 1-24