Alarm Signals - Rivacold STH009 Manual De Uso Y Mantenimiento

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

UK
*ATTENTION:
**ATTENTION:

5.2. Alarm signals

If an alarm arises the circuit starts up the following:
the display shows the related alarm code. Specifically the controller displays the alarm code and the temperature normally
displayed alternatively;
the alarm LED is lit;
the alarm relay is activated.
For some alarms and alerts the led and/or the relay are not activated. By pressing any button the relay turns off (if activated) and
the led flashes, while the alarm code remains displayed. The led turns off and the alarm code disappears only when the problem
is resolved. Table 7 explains each alarm and related actions to be undertaken.
Code
Description/Control
displayed
E1
cold room probe temperature error
if a probe is used for adjustment, the compressor will be activated
cyclically and defrosting cycles will be disabled;
if a balanced network probe is enabled, adjustment will continue,
bypassing the malfunctioning probe
E2
End defrostin probe g error
defrosting will end due to timeout
E3
3
rd
probe error (condenser temperature)
the associated controls are disabled
3
rd
probe error (2nd evaporator temperature)
defrosting will end due to timeout
heat alarm (*)
adjustment is disabled
HP pressure switch alarm(*)
adjustment is disabled
LP pressure switch alarm(*)
adjustment is disabled
E4
repeated heat alarm
adjustment is disabled permanently
E5
repeated HP pressure switch alarm
adjustment is disabled permanently
E6
repeated LP pressure switch alarm
adjustment is disabled permanently
LO
low temperature alarm
HI
high temperature alarm
EE
data saving alarm
default parameters are loaded
Ec
condenser cleaning alarm
Er
network alarm (**)
Ed
defrosting timeout alarm
Od
door open timeout alarm
normal operation is enabled again
nx
slave x alarm (on master only)
Ux
slave x not connected (on master only)
the slave is not controlled
u0
master not connected (on slave only)
the slave is released from the network and operates autonomously
dx
slave x download failed(on master only)
(*) Nothing is displayed.
(**) A network alarm is an alarm propagated by the master to all the network devices, when so programmed, if the alarm relay is
activated on the master itself.
Under certain operating conditions, the signals listed on Tabella 8 are displayed.
To unlock the keyboard, simultaneously press "SET" and "ON/OFF" for at least 5 seconds.
the "LAN" network parameter is only used in case of MASTER/SLAVE and TELEMANAGEMENT
functioning.
Table 7 – Alarms description
.
LED
Relay
Reset Mode
enable
enable
yes
yes
automatic when the condition
ceases
yes
yes
automatic when the condition
ceases
blink.
no
automatic when the condition
ceases
yes
yes
yes
no
automatic when the condition
ceases
yes
no
automatic when the condition
ceases
yes
no
automatic when the condition
ceases
yes
yes
at switch on
yes
yes
at switch on
yes
yes
at switch on
yes
yes
automatic when the condition
ceases
yes
yes
automatic when the condition
ceases
yes
yes
at power-on or after the
parameter has been stored to
memory
blink.
no
automatic when the condition
ceases
yes
yes
automatic when the condition
ceases
blink.
no
automatic at the start of the
next defrost
blink.
no
automatic when the condition
ceases
yes
progr.
automatic when the condition
ceases
blink.
no
automatic when the condition
ceases
blink.
no
automatic when the condition
ceases
blink.
no
manual or automatic when
the condition ceases
ST-SP Pag. 54 Rev 00 02/10