WIKA TR10-L Manual De Instrucciones página 31

Termorresistencia y termopar protección antideflagrante, tipo de protección contra ignición (ex d)
Ocultar thumbs Ver también para TR10-L:
Idiomas disponibles

Idiomas disponibles

9. Specifications
Measuring element of thermocouple
Validity limits of the class accuracy in accordance with ASTM E230
Type K
Type J
Type E
Type N
Type T
The table shows the temperature ranges listed in the respective standards, in which the
tolerance values (class accuracies) are valid.
The actual operating temperature of the thermometer is limited both by the maximum
permissible operating temperature and the diameter of the thermocouple and the
sheathed cable, as well as by the maximum permissible working temperature of the
thermowell/protection tube material.
For the tolerance value of thermocouples, a cold junction temperature of 0 °C [32 °F]
has been taken as the basis.
WIKA operating instructions, models TR10-L, TC10-L, TR10-0, TC10-0 (Ex d)
Standard
0 ... 1,260 °C [32 ... 2,300 °F]
Special
0 ... 1,260 °C [32 ... 2,300 °F]
Standard
0 ... 760 °C [32 ... 1,400 °F]
Special
0 ... 760 °C [32 ... 1,400 °F]
Standard
0 ... 870 °C [32 ... 1,598 °F]
Special
0 ... 870 °C [32 ... 1,598 °F]
Standard
0 ... 1,260 °C [32 ... 2,300 °F]
Special
0 ... 1,260 °C [32 ... 2,300 °F]
Standard
0 ... 370 °C [32 ... 698 °F]
Special
0 ... 370 °C [32 ... 698 °F]
EN
31