The user is responsible for connecting the power supply
cord to the connection block located behind the back
panel access cover.
This appliance may be connected by means of permanent
"hard wiring" (flexible armored or nonmetallic shielded
copper cable), or by means of a power supply cord. Only a
power supply cord kit rated at 125/250 volts minimum, 40
amperes minimum and marked for use with ranges shall be
used. See chart (below) for cord kit connection opening size
rating information. Cord must have either 3 or 4 conductors.
Appliance Rating Watts
Minimum Conductor Size,AWG
120V/208V
LlandL2
Neutral
Ground
Conductors
Conductor
Conductor
0-3120
16
16
14
3121-3900
16
16
12
3901-4160
14
16
12
4161-5200
14
16
10
5201-5570
12
16
10
5571-7430
12
14
10
7431-7800
12
12
10
7801-12500
10
12
10
12501-14500
8
12
10
Appliance Rating Watts
Minimum Conductor Size,AWG
120V / 240V
L1 and L2
Neutral
Ground
Conductors
Conductor
Conductor
0-3600
16
16
14
3601-4500
16
16
12
4501-4800
14
16
12
4801-6000
14
16
10
6001-6425
12
16
10
6426-8749
12
12
10
8750-14500
10
12
10
14501-16500
10
10
10
16501-24000
8
10
8
For mobile homes, new installations, recreational
vehicles, or areas where local codes do not permit
grounding through neutral, a 4 conductor power supply
cord kit rated at 125/250 volts minimum, 40 amperes
and marked for use with ranges should be used (see
Figure 4).
Terminals on end of wires must be either closed loop or
open-end spade lugs with upturned ends. Cord must
have strain-relief clamp.
Range Connection
Opening
Size Chart
Refer to chart below for proper range connection
opening
size and
power supply cord kit ampere rating information.
See serial plate
on range for kilowatt
rating data.
See Serial Plate on Range
Minimum
Diameter (inches)of
Range
forKW
Rating
Cord kit
Connection
Opening
120/240 Volts 120/208 Volts
Ampere
Cord Kit
DirectConnection
Rating
0-16.5 Kw
0-12.5 Kw
40 Amp
1-3/8 in.
1-1/8 in.
16.6-22.5 Kw
12.6-18.5 Kw
50Amp
1-3/8in.
1-3/8in.
Figure I
NOTE: Dual fuel Slide-in Range is shipped from factory
with 1 1/8" dia. hole as shown on figure 3. If a larger hole
is required, punch out the knockout.
Risk of fire or electrical
shock exists if
the incorrect
amperage
cord is used, the
Installation
instructions are not followed,
or the
strain relief bracket
is discarded
(see Figure 3).
Do not loosen the nuts which secure
the factory-installed
range wiring
to terminal
block
while
connecting
range. Electrical failure
or loss of
electrical
connection
may occur.
Electrical
Connection
to the Range
This appliance is manufactured
with the neutral terminal
connected to the frame.
Note: Refer to the wiring diagram in the center pages of
this manual.
Electrical
Shock
Hazard
• Electrical
ground
is required
on this appliance.
Do not connect
to the electrical
supply until
appliance
is permanently
grounded.
Disconnect
power
to the circuit breaker
or fuse
box before making
the electrical
connection.
This appliance
must be connected
to a
grounded,
metallic,
permanent
wiring
system,
or a grounding
connector
should
be connected
to the grounding
terminal
or wire lead on the
appliance.
• Do not use the gas supply line for grounding
the appliance.
Failure to do any of the above could result in a
fire, personal
injury
or electrical
shock.
Three
Conductor
Wire
Connection
to
Range
(The 3-conductor
cord or cable must be replaced with a
4-conductor cord or cable where grounding through the
neutral conductor is prohibited in new installations,
mobile homes, recreational vehicles or in other areas
where local codes do not permit neutral grounding)
If local codes permit connection of the frame grounding
conductor to the neutral wire of the copper power supply
cord (see Figure 3):
,
Remove the 3 screws at the lower end of the rear
wire cover, then bend the lower end of the rear wire
cover (access cover) upward to expose range
terminal connection
block (see Figure 2).
Figure 2
BEND REARWIRE COVER
HERE FOR ACCESS TO
TERMINAL BLOCK
loading

Este manual también es adecuado para:

7904103980079041039804790410398017904104380179041043802