Factory default settings
13.10 Sensor settings Polytron
13.10.1 Gas settings
This function sets the gas type, measuring range and units of
measurement. Only certain sensors support these settings.
1. Select Settings > Sensor > Gas settings and confirm.
 The current measured gas is displayed.
2. Select a measured gas from the list and confirm.
 The current unit of measurement is displayed.
3. Select the unit of measurement from the list and confirm.
 If the unit of measurement is set to %LEL, %UEG, or
%LIE, the category will be displayed. Continue with
step 4.
 Otherwise the current full scale deflection is displayed.
Continue with step 6.
4. Select a category and confirm.
5. Set the LEL value and confirm.
6. Set the full scale deflection and confirm.
 The new full scale deflection is displayed.
7. Select Next and confirm.
 An overview of the new gas settings is displayed.
8. After review, select Back to menu or Confirm.
Back to menu
Confirm
9. Check the alarm settings after changing the category or
the LEL value.
14
Factory default settings
14.1 Unchangeable settings for relay, LED,
and alarm
Setting
Fault relay:
Energized / Normally Open
Yellow LED:
Lit if a fault message is available
Red LED:
Single flash if A1 alarm is present. Dou-
ble flash if A2 alarm is present. If an
alarm is configured as acknowledge-
able and the alarm is acknowledged,
single/double flash changes to continu-
ously lit.
38
®
87x0 IR
Select Back to menu for leav-
ing the function without
changes and confirm with
[OK].
Select Confirm to accept the
settings and confirm with
[OK].
Setting
Alarm Hierarchy
A2 overrides A1 on the LED. However,
the A1 and A2 relays operate inde-
pendently. (Example: if A1 is acknowl-
edgeable, A2 is not, and the gas
concentration is such that it triggers A1
and A2: acknowledging the alarm will
cause the A1 relay to release. But the
red LED continues its double flash as
long as the state that triggers the A2
alarm persists.
14.2 Settings which can be changed via
the menu
Menu
Default setting
Relay active on
Active on alarm
alarm / No alarm
A1 alarm: direction Rising (falling for
O
sensors)
2
A2 alarm: direction Rising
A1 latch mode
Non-latching
A2 latch mode
Latching
A1 acknowledge
Acknowledgeable
mode
A2 acknowledge
Not acknowledge-
mode
able
Normal operation
Energized
A1 relay
Normal operation
A2 relay
Calibration pass-
_ _ _ 1
word
Settings password _ _ _ 2
LCD setting
On
SIL status
Off
Language
EN
Automatic calibra-
Off
tion
Function key
Error
Interface
Default setting
Fault current
1.2 mA
Warning
Off
Warning current
3.0 mA
Warning cycle
10 s
interval T1
Instructions for use
Range
On/Off
Falling/Rising
Latching/Non-
latching
Acknowledge-
able/Non-acknowl-
edgeable/Pre-
acknowledgeable
Energized/Not
energized
On/Off
On/Off
DE / EN / FR / ES /
RU / ZH
On/Off
Graphic, fault,
warning, vitality,
bump test
Range
0 to 3.5 mA
On/Off
0 to 3.5 mA
5 to 60 s
®
|
Dräger Polytron
8000 Series