Bosch Climate 2000 Manual De Instalación página 30

Ocultar thumbs Ver también para Climate 2000:
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 34
Commissioning
▶ Remove the cover of the interface panel [1].
▶ Remove the screws. And take off the strain relief [2] of the
connecting terminal ( Fig. 70).
▶ Knock out an opening for the cable feed [3] on the rear of the indoor
unit and feed the cable through.
▶ Secure the cable on the strain relief [2] and connect to the
connecting terminals W, 1(L), 2(N), S and
▶ Note assignment of wires to the terminals.
▶ Reattach the covers.
▶ Route the cable to the outdoor unit.
3.5.3
Connecting the outdoor unit
A power cable (3-core) is connected to the outdoor unit and the
communication cable is connected to the indoor unit (5-core). Use
cables of the type H07RN-F with sufficient conductor cross-section and
protect the mains power supply with a fuse ( Table 36).
Outdoor unit
Mains fuse
protection
CL2000 26 E
13 A
CL2000 35 E
13 A
CL2000 53 E
16 A
CL2000 70 E
25 A
Table 36
▶ Undo the screw and remove the cover of the electrical connection
( Fig. 71).
▶ Secure the communication cable to the strain relief and connect to
the terminals W, 1(L), 2(N), S and
terminals same as indoor unit) ( Fig. 72).
▶ Secure power cable to the strain relief and connect to the terminals
L, N and
.
▶ Reattach cover.
4
Commissioning
4.1
Commissioning checklist
1
Outdoor unit and indoor unit are correctly installed.
2
Pipes are correctly
• connected,
• thermally insulated,
• and checked for tightness.
3
Condensate pipes are functioning correctly and
have been tested.
4
Electrical connection has been correctly
established.
• Power supply is in the normal range
• Protective conductor is properly attached
• Connection cable is securely attached to the
terminal strip
5
All covers are fitted and secured.
6
The horizontal louver of the indoor unit is fitted
correctly and the actuator is engaged.
Table 37
30
.
Conductor cross-section
Power cable Communication
cable
2
2
≥ 1.5 mm
≥ 1.5 mm
2
2
≥ 1.5 mm
≥ 1.5 mm
2
2
≥ 1.5 mm
≥ 1.5 mm
2
2
≥ 2.5 mm
≥ 2.5 mm
(assignment of wires to
4.2
Function check
The system can be tested once the installation including tightness test
has been carried out and the electrical connection has been established:
▶ Connect the power supply.
▶ Switch on indoor unit with the remote control.
▶ Press the Mode button to set the cooling mode (').
▶ Press arrow key (/) until the lowest temperature is set.
▶ Test cooling mode for 5 minutes.
▶ Press the Mode button to set the heating mode (%).
▶ Press arrow key (.) until the highest temperature is set.
▶ Test heating mode for 5 minutes.
▶ Ensure freedom of movement of air baffle.
If the room temperature is less than 17 °C, the cooling mode must be
switched on manually. This manual operation is only envisaged for
testing and emergency situations.
▶ Otherwise, always use the remote control.
To switch on the cooling mode manually:
▶ Switch off the indoor unit.
▶ Open the upper cover of the indoor unit and lock in place.
▶ Press the Manual Control button ( Fig. 73) twice to start manual
cooling mode.
▶ Carry out the function check as usual.
▶ Press the Manual Control button again to switch off the indoor unit.
▶ Close the top panel.
4.3
Handover to the user
▶ When the system has been set up, hand over the installation manual
to the customer.
▶ Explain to the customer how to use the system, referring to the
operation manual.
▶ Advise the customer to carefully read the operation manual.
5
Troubleshooting
5.1
Faults with indication
WARNING
Risk to life from electric shock!
Touching live electrical parts can cause an electric shock.
▶ Before working on electrical parts, disconnect all phases of the
power supply (fuse/circuit breaker) and lock the isolator switch to
prevent unintentional reconnection.
If a fault occurs during operation, a fault code (e.g. EH 02) appears on
the display.
If a fault is present for more than 10 minutes:
▶ Briefly interrupt the power supply and switch the indoor unit back on.
If a fault persists:
▶ Call customer service and provide the fault code and details of the
appliance.
Climate 2000 – 6721852025 (2024/01)
loading

Este manual también es adecuado para:

Cl2000u w 26 eCl2000u w 35 eCl2000u w 53 eCl2000u w 70 eCl2000 26 eCl2000 35 e ... Mostrar todo