1) Turn off the UPS.
2) Unplug the input cord from the mains socket.
3) Using a Phillips head screwdriver, remove the four black screws located on the sides of the UPS
(step 1 picture).
4) Place the front plate on the top of the UPS for easy access to the battery connections (step 2
picture).
5) Disconnect the red connector from the battery pack (step 3 picture).
6) Using a Phillips head screwdriver, remove the sliver screws from the silver battery pack
retaining plate. KEOR SPE 750-1000 has two screws, KEOR SPE 1500-2000-3000 has four screws
(step 4 picture).
Step 5 - Pull on the transparent tab to slide the battery pack out of the UPS.
6.2
Battery information
Model
750 VA
1000 VA
1500 VA
2000 VA
3000 VA
6.3
Fuse replacement
The input socket includes a fuse for 750-1000-1500 VA models. If the fuse must be replaced,
unplug the input cord, and use a screwdriver to remove the fuse from the holder.
Instead, there is a dedicated fuse holder for the 2000- 3000 VA models.
Model
750 VA
1000 VA
1500 VA
2000 VA
3000 VA
60
Battery source 1
2 pcs Minhua type MS7-12
2 pcs Minhua type MS9-12
3 pcs Minhua type MS9-12
4 pcs Minhua type MS9-12
4 pcs Minhua type MS9-12
2 pcs Ritar type RT1270
2 pcs Ritar type RT1290
3 pcs Ritar type RT1290
4 pcs Ritar type RT1290
4 pcs Ritar type RT1290EP
INPUT FUSE
F10AH250V
(5 x 20 mm)
F20AH250V
(6,3 x 32mm)
6 Maintenance
Battery source 2