5. Electrical work
5.3. Types of control cables
1. Wiring transmission cables
Shielding wire
Types of transmission cable
Use UL wire rated 300 V
Cable diameter
More than 1.25 mm² (AWG16)
Length
Less than 200 m, 219 yard
2. M-NET Remote control cables
Shielding wire
Types of remote control cable
Use UL wire rated 300 V
Cable diameter
0.5 (AWG20) to 1.25 mm² (AWG16)
Add any portion in excess of 10 m, 33 ft to within the longest
Length
allowable transmission cable length 200 m, 219 yard.
3. MA Remote control cables
2-core cable (unshielded)
Types of remote control cable
Use UL wire rated 300 V
Cable diameter
0.3 (AWG22) to 1.25 mm² (AWG16)
Length
Less than 200 m, 219 yard
1
B
A
M1 M2
M1 M2
TB3
TB5
B
2
M1 M2
TB3
TB5
3
B
CN90
M1 M2
Pair No.
0
TB3
9
TB5
D
Pair No.
E
0
Fig. 5-8
A
BRANCH
10s
1s
No.
DIGIT
DIGIT
Fig. 5-9
A
S
1
2
M1 M2
S
1
2
TB15 TB5
TB15
C
C
A
A
M1 M2
S
M1 M2
S
TB5
C
C
A
M1 M2
S
1
2
TB15
5.4. Connecting remote controller, indoor and out-
door transmission cables (Fig. 5-8)
• Connect indoor unit TB5 and outdoor unit TB3. (Non-polarized 2-wire)
The "S" on indoor unit TB5 is a shielding wire connection. For specifi cations about
the connecting cables, refer to the outdoor unit installation manual.
• Install a remote controller following the manual supplied with the remote controller.
• Connect the remote controller's transmission cable within 10 m, 33 ft using a
2
0.75 mm
(AWG18) core cable. If the distance is more than 10 m, 33 ft, use a 1.25
mm
2
junction cable.
1
MA Remote controller
• Connect the "1" and "2" on indoor unit TB15 to a MA remote controller. (Non-polarized
2-wire)
• DC 9 to 13 V between 1 and 2 (MA remote controller)
2
M-NET Remote controller
• Connect the "M1" and "M2" on indoor unit TB5 to a M-NET remote controller. (Non-
polarized 2-wire)
• DC 24 to 30 V between M1 and M2 (M-NET remote controller)
3
Wireless remote controller(When installing wireless signal receiver)
• Connect the wire of wireless signal receiver (9-pole cable) to CN90 of indoor control-
ler board.
• When more than two units are run under group control using wireless remote
controller, connect TB15 each with the same number.
• To change Pair No. setting, refer to installation manual attached to wireless remote
controller. (In the default setting of indoor unit and wireless remote controller, Pair
No. is 0.)
A
Terminal block for indoor transmission cable
B
Terminal block for outdoor transmission cable (M1(A), M2(B),
C
Remote controller
D
Wireless signal receiver
E
Wireless remote controller
5.5. Setting addresses (Fig. 5-9)
(Be sure to operate with the main power turned OFF.)
• There are 2 types of rotary switch setting available: setting addresses 1 to 9 and
over 10, and setting branch numbers.
1
How to set addresses
Example: If Address is "3", remain SW12 (for over 10) at "0", and match
SW11(for 1 to 9) with "3".
2
How to set branch numbers SW14 (Series R2 only)
Match the indoor unit's refrigerant pipe with the BC controller's end connection
number.
Remain other than series R2 at "0".
• The rotary switches are all set to "0" when shipped from the factory. These switches
can be used to set unit addresses and branch numbers at will.
• The determination of indoor unit addresses varies with the system at site. Set them
referring to the Data Book.
A
Address board
(S))
en