Mitsubishi Electric CITY MULTI PLFY-WL-NEMU-E Serie Manual De Instalación página 10

Idiomas disponibles

Idiomas disponibles

5. Electrical work
A
~208/230V
~208/230V
Total operating current of the indoor unit
F0 = 16 A or less *2
F0 = 25 A or less *2
F0 = 32 A or less *2
Apply to IEC61000-3-3 about max. permissive system impedance.
*1 The Ground-fault interrupter should support inverter circuit.
The Ground-fault interrupter should combine using of local switch or wiring breaker.
*2 Please take the larger of F1 or F2 as the value for F0.
F1 = Total operating maximum current of the indoor units × 1.2
F2 = {V1 × (Quantity of Indoor unit 1)/C} + {V1 × (Quantity of Indoor unit 2)/C} + {V1 × (Quantity of Indoor unit 3)/C} + ···
~ 230 V
Indoor
unit 1
Indoor unit
PLFY-NEMU, PMFY-NBMU, PEFY-NMSU,
Type 1
PCFY-NKMU, PKFY-NHMU, PKFY-NKMU, PLFY-NFMU
Type 2
PEFY-NMAU
Type 3
PEFY-NMHSU
Others
Other indoor unit
• V1 and V2
V1 and V2 are the breaker coefficient.
V1: Breaker coefficient of rated current
V2: Breaker coefficient of current sensitivity
The values of V1 and V2 differ from depending on the model. Therefore, please refer to IM of each model.
• C : Multiple of tripping current at tripping time 0.01 s
Please pick up "C" from the tripping characteristic of the breaker.
<Example of "F2" calculation>
• Condition PLFY-NEMU × 4 + PEFY-NMAU × 1, C = 8 (refer to right sample chart)
V1 of PLFY-NEMU = 19.8, V1 of PEFY-NMAU = 38
F2 = 19.8 × 4/8 + 38 × 1/8
= 14.65
→ 16 A breaker (Tripping current = 8 × 16 A at 0.01 s)
*3 Current sensitivity is calculated using the following formula.
G1 = V2 × (Quantity of Indoor unit 1) + V2 × (Quantity of Indoor unit 2) + V2 × (Quantity of Indoor unit 3) + V2 × ···
+ V3 × (Wire length [km])
<Example of "G1" calculation>
*Condition : PKFY-NLMU × 2 + PLFY-NEMU × 2 + PEFY-NMAU × 1
V2 of PKFY-NLMU = 2.4, V2 of PLFY-NEMU = 2.4, V2 of PEFY-NMAU = 1.6, Wire thickness and length: 1.5 mm
en
G1 = 2.4 × 2 + 2.4 × 2 + 1.6 × 1 + 48 × 0.2
= 20.8
As a result, current sensitivity is 30 mA 0.1 sec or less.
G1
30 or less
100 or less
8
D
B
C
C
C
C
A
B
D
L1 L2 GR
M1
M2
S
1 2
C
TB2
TB5
TB15
Fig. 5-7
Minimum wire thickness (mm², AWG.No)
Main cable
Branch
1.5, AWG14
1.5, AWG14
2.5, AWG13
2.5, AWG13
4.0, AWG11
4.0, AWG11
Indoor
Indoor
Indoor
unit 1
unit 2
unit 3
Current sensitivity
30 mA 0.1 sec or less
100 mA 0.1 sec or less
5.2. Power supply wiring
• Wiring size must comply with the applicable local and national codes.
• Use copper supply wires.
C
Use UL wires rated 300 V or more for the power supply cords.
• Install a ground wire longer than other cables.
• A switch with at least 3 mm, 1/8 inch contact separation in each pole shall be
provided by the air conditioner installation.
[Fig. 5-7]
A
Ground-fault interrupter
B
Local switch/Wiring breaker
C
Indoor unit
D
Pull box
Warning:
Never splice the power cable or the indoor-outdoor connection cable,
otherwise it may result in a smoke, a fire or communication failure.
Ground-fault interrupter *1
Ground
1.5, AWG14
20 A current sensitivity *3
2.5, AWG13
30 A current sensitivity *3
4.0, AWG11
40 A current sensitivity *3
Indoor
unit 3
V1
V2
19.8
2.4
38
1.6
13.8
4.8
0
0
2
Wire thickness (mm
/AWG)
V3
2.1/14
48
3.3/12
56
5.3/10
66
Local switch (A)
Breaker for wiring
Capacity
Fuse
(NFB)
16
16
25
25
32
32
Sample chart
6000
600
SAMPLE
60
10
1
0.1
0.01
1
2
3
4
6
Rated Tripping current (x)
2
(AWG14) 0.2 km
20
30
40
8
10
20
C
loading