Mitsubishi Electric TRANE CITY MULTI TPKFYP HM142 Serie Manual De Instalación página 6

Ocultar thumbs Ver también para TRANE CITY MULTI TPKFYP HM142 Serie:
Idiomas disponibles

Idiomas disponibles

4. Installing the refrigerant piping
A
B
45°±2°
Fig. 4-1
A Flare cutting dimensions
Copper pipe O.D.
Flare dimensions
(mm, inch)
øA dimensions (mm, inch)
ø6.35, 1/4"
8.7 - 9.1, 11/32 - 23/64
ø9.52, 3/8"
12.8 - 13.2, 1/2 - 33/64
ø12.7, 1/2"
16.2 - 16.6, 41/64 - 21/32
ø15.88, 5/8"
19.3 - 19.7, 49/64 - 25/32
Liquid pipe
Pipe size O.D.
(mm, inch)
ODø6.35
P008, P012, P015
1/4"
ODø6.35
P018
1/4"
E Apply refrigerating machine oil over the entire flare seat surface.
TPKFYP·HM142
D
1-11/16
25/32
B
Fig. 4-3
6
(inch)
C
R410A
Gas pipe
Tightening
Tightening
Pipe size O.D.
torque.
(mm, inch)
(N·m, ft·lbs)
(N·m, ft·lbs)
14 - 18
ODø12.7
10 - 13
1/2"
14 - 18
ODø12.7
10 - 13
1/2"
35-23/64
21-7/32
17-63/64
( C )
15-3/4
F
F
2-13/64
Fig. 4-2
A
4.1. Connecting pipes (Fig. 4-1)
• When commercially available copper pipes are used, wrap liquid and gas pipes
with commercially available insulation materials (heat-resistant to 100 °C, 212 °F
or more, thickness of 12 mm, 1/2 inch or more).
• The indoor parts of the drain pipe should be wrapped with polyethylene foam
insulation materials (specific gravity of 0.03, thickness of 9 mm, 23/64 inch or
D
more).
• Apply thin layer of refrigerant oil to pipe and joint seating surface before
tightening flare nut.
• Use two wrenches to tighten piping connections.
• Use refrigerant piping insulation provided to insulate indoor unit connections.
Insulate carefully.
B Refrigerant pipe sizes & Flare nut tightening torque
C Do not apply refrigerating machine oil to the screw portions.
(This will make the flare nuts more apt to loosen.)
D Be certain to use the flare nuts that are attached to the main unit.
(Use of commercially-available products may result in cracking.)
Flare nut O.D.
Liquid pipe
Gas pipe
torque.
(mm, inch)
(mm, inch)
49 - 61
17
26
35 - 44
43/64
1-1/16
49 - 61
17
26
35 - 44
43/64
1-1/16
( B )
6-7/32
1-11/16
( A )
6-21/32
7-7/32
1-27/32
2-23/64
5-5/16
4.2. Positioning refrigerant and drain piping (Fig. 4-2)
 TPKFYP·HM142
Gas pipe
* Indicates the condition with accessories mounted.
A
Liquid pipe
B
Drain hose
C
Left-side piping knockout hole
D
Right-side piping knockout hole
E
Lower piping knockout hole
F
Mount board
G
1
4.3. Refrigerant piping (Fig. 4-3)
Indoor unit
1. Remove the flare nut and cap of the indoor unit.
2. Make a flare for the liquid pipe and gas pipe and apply refrigerating machine oil
(available from your local supplier) to the flare sheet surface.
3. Quickly connect the on site cooling pipes to the unit.
4. Wrap the pipe cover that is attached to the gas pipe and make sure that the
connection join is not visible.
5. Wrap the pipe cover of the unit's liquid pipe and make sure that it covers the
insulation material of the on site liquid pipe.
6. The portion where the insulation material is joined is sealed by taping.
Site-side refrigerant piping
A
Unit side refrigerant piping
B
(inch)
G
E
loading