3 Press the RESET button to reset. The unit then
reverts to the last operating mode selected.
▷ Possible faults:
Display
F
A
C
E
U
4 If the burner control unit does not respond even
though all the possible faults have been rectified
as described below, contact your supplier.
? Fault
! Cause
• Remedy
? The 7-segment display has gone out despite
the voltage supply being OK?
! Fuse F2 is defective.
• Check the fuse contacts.
L
N
There is a spare fuse directly next to the fuse
holder.
Attention! Fit the correct fuse for 4 A.
? Error code F. and 1 flash alternately?
On burner start-up, the burner control unit has
not detected a flame during the safety time. Sev-
eral automatic start-up attempts will be com-
D – 49018 Osnabrück, Germany
pleted if a restart has been programmed.
ACU
! Inadequate inlet pressure available.
• Check the inlet pressure.
! Ignition is not working properly.
• Check the connection of the ignition cables for
damage or moisture. The spark plug must be
fitted correctly.
• Check the ignition spark acoustically during the
3-second ignition time from the burner fan side.
• Clean the spark electrode.
• Check the ignition transformer and replace it if
necessary.
! Poor flame signal due to incorrect burner adjust-
ment.
• Readjust the CO
ing the heater).
RGA100_NF.indd 15
Fault type
Flame fault
Air fault
Temperature fault
Electronics fault
Other possible faults
L
N
L
N
N
value, see page 10 (Adjust-
2
! Poor flame signal due to dirty or badly connected
flame rod.
• Check the flame rod and clean it with fine abra-
sive paper if necessary.
• Check the cable connection, cable and terminal
boot for damage or moisture. The terminal boot
must be fitted correctly.
• Check the yellow and green burner ground cable
for corrosion and to ensure it is firmly connected.
• The flame rod is defective and must be replaced.
! Air in the gas pipe.
• Vent the gas pipe.
! Valves do not open.
• Disconnect the valve plug on the gas combina-
tion control and measure the voltage at the valve
plug during the safety time.
• If the voltage is not adequate, first check fuse F2
(4 A). If the display and the LEDs are not lit, it is
defective.
• If the voltage is not adequate, replace the gas
combination control and return it to the supplier.
LT
LV
? Error code F. and 1 flash alternately and the
1
2
L
i
light is red?
The fault could not be rectified. All start-up at-
tempts have been used and the burner control
unit goes into lock-out.
▷ Reset is only possible by pressing the RESET
button on the burner control unit or using the
remote reset if there is one.
• Rectify the cause of the fault as described above
for warning F.1.
? Error code F. and 2 flash alternately?
The flame has gone out during operation. If a
restart has been programmed, an automatic
restart will be completed.
! Poor flame signal due to incorrect burner adjust-
ment.
• Readjust the CO
ing the heater).
! Poor flame signal due to dirty or badly connected
flame rod.
• Check the flame rod and clean it with fine abra-
sive paper if necessary.
• Check the cable connection, cable and terminal
boot for damage or moisture. The terminal boot
must be fitted correctly.
• Check the yellow and green burner ground cable
for corrosion and to ensure it is firmly connected.
• The flame rod is defective and must be replaced.