Anselmo Cola GRACE 13 Manual De Instalación, Uso Y Mantenimiento página 35

Idiomas disponibles
  • ES

Idiomas disponibles

2.2 Place of installation, positioning and fire-prevention safety
The place of installation must be sufficiently ventilated to allow the removal of any combustion smoke leaks.
The unit is suitable for operation in domestic environments with min. temperature not below 0°C.
To prevent the risk of fire, the structures surrounding the stove must be protected from the heat.
Floors in wood or in any flammable material must be suitably protected at the base with steel or toughened glass
panels; the protection must cover the base and also a certain area in front of the stove.
Any wooden boards or beams above or crossed by the flue must be suitably protected in conformity with the
requirements of the specific current installation standards.
The minimum front distance for the protection of flammable objects is 1.5 m. The minimum safety distances from
flammable materials must comply with the ref. fig.2.
Every installation must provide for an easily accessible technical space for periodical maintenance.
The stove is provided with 4 adjustable feet to facilitate positioning on not perfectly flat floors. To adjust the height,
tilt the stove slightly and turn the feet as required.
The stove is supplied with the ambient sensor fixed through a wrapper on the back of the stove; we recommend to
remove the wrapper and to locate the sensor in the best position possible as to improve the temperature registration
in accordance with the ambient context and the length of the cable.
As for temperature registration done at a certain distance we reccomend to install the ambient thermostat/ambient
programming clock-thermostat – see. par.4.8.
- The stove cannot be installed in bedrooms, bathrooms and in general in rooms where
another heating unit is already installed without an independent air inflow.
- With wooden floors, install a floor protection base in conformity with the current regulations.
- Suitable fire-prevention devices should be arranged for any eventuality.
- Do not install the stove in places with an explosive atmosphere.
2.3 Air inlet
The stove air inlet pipe or intake is located at the back and is round and 50 mm in diameter.
A quantity of air at least equal to that necessary for combustion must flow in the room where the stove is installed;
therefore the combustion air necessary to ensure correct operation of the stove must be drawn:
from the room, provided there is a wall air inlet near the stove, communicating with the outside and of minimum
area 100 cm² suitably protected externally by a grille;
or with direct connection to the outside with an appropriate pipe having a minimum internal diameter of 50 mm
and maximum length of 1.5 m, provided with antiwind protection at the end (down bend).
The air inflow can also be obtained from a room adjoining that of installation, provided the flow can occur freely
through permanent openings to the outside; the room must not be used as a garage, for storing combustible
materials or for activities with fire risk.
2.4 Fume exhaust
The fumes can be exhausted through a connection to a conventional flue or an external duct with double wall or
insulated pipe. The fume exhaust connections must guarantee a minimum draught of 10 Pa so that the evacuation
of fumes is assured in case of a temporary power failure.
- The installer must check the efficiency and state of the flue and its conformity with the
local, national and European regulations.
- Certified pipes and connections with adequate seals guaranteeing their tightness must be used.
- In case of fire, shut down the stove, promptly call the fire department, and avoid continual attempts
to extinguish it.
- Clean the flue and respective connection at least once a year.
2.4.1Types of installation
Listed below are definitions and requirements for correct installation of an exhaust flue in accordance with Italian
Standard UNI10683:
FLUE : a vertical duct for collecting and expelling, at an appropriate height
from ground, the fumes coming from a single unit and, where permitted,
more than than one.
FLUE technical requirements :
- it must be fumetight, isolated and insulated depending on its use;
- it must have a mainly vertical path with axis deviation < 45°;
- it must be at a suitable distance from flammable materials with insulation
or air gap;
- it must preferably have a constant, free and independent round internal
section;
- it is advisable for the flue to have an inspectionable chamber for the
collection of solid materials
- and any condensate, placed under the beginning of the fume duct.
Min. distance 0.2 m
35
Antiwind
Comignolo
grille
antivento
Canna
fumaria
Flue
Distanza min 0.2m
Flue
Raccordo
connection
fumi
Camera
Inspectionable
ispezionabile
chamber
Presa d'aria
Ext. air inlet
esterna
min.100 cm 2
2
min.100 cm
GRACE 13
loading