OPTIONAL FUNCTION
No.
Item
Optional function
36
Not available
d7
37
Not Used
e1
38
Not Used
e2
39
Not used
E3
40
Not Used
e4
41
Not used
E5
Period of indoor fan
42
operation after cooling
E6
operation stoppage
43
Not used
E7
Control for stop of the indoor
unit fan during heating
thermo OFF conditions (with
44
remote sensor THM-R2AE
E8
connected to the THM4
connector in the indoor unit
PCB)
45
Not Used
eg
46
Not used
EA
Indoor unit fan control
47
during cooling thermo OFF
Eb
conditions
Forced thermo ON when
48
EC
stopping in cooling operation
49
Not used
Ed
Control in "Automatic" indoor
50
EE
fan speed mode
14
PMML0497 rev.1 - 12/2020
Individual
Settings
Setting
"- -"
-
permanent
00
-
-
01/02
00
-
-
01
00
-
-
01
00
-
-
01/02
00
-
-
01
Disabled function
00
(factory setting)
01
60 minutes
02
120 minutes
00
-
-
01
00
Fan operation in Low speed
01
Fan stop in thermo OFF conditions.
00
-
-
01
00
01
-
-
02
Function disabled
00
(factory setting)
01
Low
02
Slow
Function disabled
00
(factory setting)
01
Enabled
00
-
-
01
Function disabled
00
(factory setting)
01
Enabled
Setting conditions
Use as 00 conditions
Use as 00 conditions
Use at 00 conditions
Use as 00 conditions
Use at 00 conditions
This function prevents the
condensation in the unit by
keeping the fan running after the
unit operation has been turned
OFF.
Use at 00 conditions
This function stops the fan
to prevent cold draughts or
overheating.
C8 must be set to 01 to use the
E8=01 setting.
The connection of a THM-R2AE
remote temperature sensor to the
THM4 port in the indoor unit PCB
is required. The remote sensor
shall be installed in a proper place
for the correct detection of room
temperature.
(In case that automatic louvre is
set, the louvre will keep operating
in both thermo ON and thermo
OFF condition.)
Use as 00 conditions
Use at 00 conditions
This function decreases speed of
the indoor unit fan during cooling
thermo OFF, to reduce the spread
of smells and humidity.
This function is used to force
thermo ON during 6 minutes when
stopping in cooling operation.
Use at 00 conditions
This function limits the speed
of the indoor fan when room
temperature is close to the setting
temperature.