Hitachi PC-ARH1E Manual De Instalación Y Funcionamiento página 17

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 35
OPTIONAL FUNCTION
7 OPTIONAL FUNCTION
1 Press and hold " " for "Temp" and "Fan" simultaneously for
at least three seconds during the normal mode (when unit is
not operated).
2 Select the optional mode by pressing " " or " " for "Temp"
and press "Fan".
01: Function
Selection
02: Input/Output
Setting
3 Select the indoor unit by pressing " " or " " for "Temp" and
press "Fan".
(This screen is NOT displayed when there is only one indoor
unit connected with the controller.
In this case, (4) will be displayed.)
7.1 OPTIONAL SETTING ITEMS
No.
Item
Optional function
Heating temperature
compensation
Models:
RCI-FSN4
RCIM-FSN4E
RCD-FSN3
RPC-FSN3
RPI-FSN5E
RPI-FSN3E(P)E(-f)
1
b1
RPIM-FSN4E(-DU)
RPk-FSN(H)3M
Heating temperature
compensation
Models:
RPF(I)-FSN2E
9
PMML0497 rev.1 - 12/2020
4 Press " " or " " for "Temp" and select the item.
5 Press "Fan" and change the setting.
6 Press " " and " " for "Temp" simultaneously to return to the
normal mode.
Individual
Settings
Setting
Normal (factory setting)
00
(Setting Temperature + 4 ºC)
No compensation
01
(Setting Temperature)
02
Setting Temperature + 2 ºC
03
Setting Temperature + 3 ºC
04
Setting Temperature + 1 ºC
RPF(I)-FSN2E: Normal
00
(factory setting)
(Setting Temperature + 2 ºC)
No compensation
01
(Setting Temperature)
02
Setting Temperature + 2 ºC
Setting conditions
This function is used to adjust the
temperature difference between
the temperature read by the
inlet sensor and the real room
temperature.
This is useful when the inlet air
thermistor is not placed inside the
indoor unit or due to uneven heat
load.
Note:
Description
The "02", "03", "04" settings
may not be available depending
on the type of indoor unit.
This setting shall be performed
separately for each indoor
unit, even in case that multiple
indoor units are connected to
one remote controller.
loading