Installation
6.3
Configuration of unit software
Before you first start up the unit, the controls can be adapted to suit the
installation conditions. This must be done by the person installing the unit.
In configuration mode, the following unit software parameters must be set
at the control panel (fig. 6 on page 5).
Menu
level
1
2
3
4
5
Note
I
Configuration mode can still be activated if the undervoltage protection
mechanism has switched off the unit and only residual voltage is
available.
6.3.1
Starting and ending configuration mode
The adjustable parameters can be changed in configuration mode:
➤ When using the ON/OFF (fig. 6 on page 5, item 1) button to switch
on the unit, hold both buttons + and – (fig. 6 on page 5, item 6 and 7)
pressed until the compressor LED flashes.
✓ You are now in configuration mode.
✓ The first digit of the digital display (fig. 6 on page 5, item 5) shows
the menu level and the second and third digits show the parameters
which can be set, e.g.
17 °C.
I
Note
If you make no entry on the control panel for 60 seconds, the unit quits
configuration mode and shuts down.
➤ Press the ON/OFF button to quit configuration mode.
Parameter
Meaning
Set temperature
The unit starts at the temperature
defined here.
Low voltage
The battery monitor shuts down the unit
cut-off
at the voltage defined here.
Operating mode
The unit starts with the operating mode
defined here.
Default settings
Parameters 1 – 3 can be reset to the
default settings.
Temperature unit
The temperature can be displayed in °C
display
or °F.
1.17
for menu level 1 and a set target value of
CoolAir
Default
setting
20 °C
Characteris-
tic figure 4 =
22.8 V
0 = Auto-
matic mode
--
°C
33