EMobility eClick Instrucciones De Instalación página 47

Para ebox smart, professional y touch
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 111
RCD
Charging power
Charging current
Example
Standards
Type
Operating voltage
Poles
Rated residual current
Rated current
Tripping time
Operating characteristic
Overvoltage category
Fouling factor
Ambient temperature
Material number
Circuit breaker
Charging power
Charging current
Example
Standards
Tripping characteristics
Poles
Rated switching capacity
Rated current
Insulation voltage
Overvoltage category
Fouling factor
Ambient temperature
Material number
• Installation of overvoltage protection equipment,
if demanded under national standards
• Routing of the connecting line to the installation site
• Connection of the supply line between the eClick / eBox
and the sub-distribution
All manuals and user guides at all-guides.com
F204A, 4-pole, 25/0.03 A ABB
DIN EN 61008-1 / DIN EN 61008-2-1
S203-NA K, 20A ABB
DIN EN 60947-1, -2 / DIN EN 60898-1
3,7 kW; 11 kW
16 A
DIN EN 61008-1 / DIN EN 61008-2-1
A
230/400 V AC
4-pole
30 mA
25 A
300 ms
instantaneous
III
2
Tmax +55 °C,
Tmin -25 °C
10284822
3,7 kW; 11 kW
16 A
DIN EN 60947-1, -2 / DIN EN 60898-1
K
4-pole
6,000 A
20 A
4 kV
III
2
Tmax +55 °C,
Tmin -25 °C
10133671
47
Installation
7,4 kW; 22 kW
32 A
F204A, 4-pole, 40/0.03 A ABB
230/400 V AC
4-pole
30 mA
40 A
300 ms
short-time delayed (AP-R)
Tmax +55 °C,
Tmin -25 °C
10118695
7,4 kW; 22 kW
32 A
S203-NA K, 40A ABB
4-pole
6,000 A
40 A
4 kV
Tmax +55 °C,
Tmin -25 °C
10118694
Caution
For space reasons, the supply
line chosen must have whenever
possible a conductor area no
greater than 6 mm².
From a thermal point of view, a
10 mm² supply cable must be
selected. In addition, the cable
cross-section of the feed line is
selected according to its length.
A
III
2
K
III
2