General and electrical
specifications
Charging power
Mains input power
Output power to eBox
Operating temperature
Storage temperature
Weight
IP
eSmartMeter
(MID compatible)
Max line cross-section
Certifications
External accessories
User protection installed
in sub-distribution per
charging port according to
the respective supply line
Short circuit / overload
protection installed
in sub-distribution per
charging port according to
the respective supply line
Circuit breakers of other manufacturers with identical characteristics
to those described here can also be used.
All manuals and user guides at all-guides.com
eClick
3.7 / 4.6 / 7.4 / 11 / 13.8 / 22 kW (16 A, 20 A, 32 A; single- or three-phase)
Three-phase current 400 V AC, 32 A (22 kW) / 20 A (13.8 kW) / 16 A (11 kW) or
single-phase alternating current 230 V AC, 32 A (7.4 kW) / 20 A (4.6 kW) / 16 A (3.7 kW)
Three-phase current 400 V AC, 32 A (22 kW) / 20 A (13.8 kW) / 16 A (11 kW) or
single-phase alternating current 230 V AC, 32 A (7.4 kW) / 20 A (4.6 kW) / 16 A (3.7 kW)
-30 °C to +50 °C (full load output at -30 °C to +50 °C)
I
MID-conform (Europe), CE Certified
Max supply line
(top or bottom):
10 mm²
CE certificate (tested and confirmed by a certified body)
eClick
32 A connection: ABB F204A-40/0.03, Type A, 4-pole
(short time delay, operating voltage: 230/400 V AC)
16 A connection: ABB F204A-25/0.03, Type A, 4-pole
(operating voltage: 230/400 V AC)
32 A connection: ABB S203-NA K40A
(rated switching capacity: 6,000 A)
16 A connection: ABB S203-NA K20A
(rated switching capacity: 6,000 A)
ePoleDuo / eClicks in ePoleDuo
eClick:
eClick:
-30 °C to +80 °C
1,1 kg
Max supply line
(bottom only):
ePoleDuo / eClicks in ePoleDuo
Type A RCD:
Circuit breaker:
Safety information
I (eClicks)
10 mm²
43