case after interruption of the air fl ow;
b) make sure compressed air does not enter the dryer when the dryer is
disconnected or if an alarm occurs.
set
c) Press
to stop the dryer (for model 120-180).
Press
to stop the dryer (for model 220-350).
&
d) Turn the MAIN SWITCH "
" to "O OFF" to switch the power off.
Y
Wc version, close the water circuit with the dryer stopped.
5 Control
(PSE120-180)
5.1 Control panel
Fig.1
QS Main power switch.
UP button: press to increase the value of a selected
editable parameter. Pressed for 3s start manual drain.
DOWN button: press to decrease the value of a selected
editable parameter.
esc
ESC button : to exit without saving;
returns to the previous level;
PRESSED FOR 5s. ALARM RESET.
set
SET button : to exit and saving/ confi rm the value;
go to the next level;
enter on Set Menu;
PRESSED FOR 5s. START DRYER.
esc
set
and
.
: press together at the same time to enter on the
parameters of the program
5.2 Symbol
Symbol
Symbol status
Function
k
Lit up
compressor ON
Off
compressor OFF
Lit up
dryer ON
Flashing
dryer OFF
Lit up
Alarm present
!
Flashing
Warning present
Off
No alarm present
English
Symbol
Symbol status
Function
q
Lit up
Condensate drain ON
Off
Condensate drain OFF
illuminated
dryer ON / Compressor OFF
Maintenance
illuminated
°C °F
grade
illuminated
Bar PSI illuminated
pressure
5.3 Parameter settings
Temperature measurement unit
How to set the temperature measurement unit.
esc
set
Press
and
together at the same time to enter general menu
"PAr" .
set
to fi nd menu " CF9" .
Press
set
Press
to enter
to fi nd the menu " A1".
Use the arrows
or
set
Press
to choose: ON : Fahrenheit / OFF: Celsius.
PSI
/
set
Press
to confi rm.
esc
Press
to exit.
esc
set
PAr
set
esc
CF9
set
esc
---
A1
set
esc
OFF
PSE 120-350
5.4 Confi guration condensate drain
There are three modes of operation:
a) CAPACITIVE = Automatic drainign using a capacitive sensor;
b) TIMED = programmable draining times;
c) CONTINUOUS (external) = if there is an external drain.
set
Press
and
"PAr" .
set
Press
to enter.
Use the arrows
set
Press
to enter.
Use the arrows
set
Press
to choose the type of the drain:
0 = external;
1 = timed;
2 = capacitive.
set
Press
for fi ve seconds to select the drain.
esc
PAr
esc
Barg
CF9
d3
esc
For the option (1) timed drain,it is possible to set the ON/OFF time of
the drain.
On menu " Cd "
Use the arrows
opening time.
set
On
Press
to confi rm.
Use the arrows
closing time.
esc
together at the same time to enter general menu
to fi nd menu " Cd "
or
to fi nd parameter " d3 "
or
set
set
........
Cd
set
esc
d2
d1
set
2
1
0
or
to fi nd the parameter "d1" to set the
to fi nd the parameter " d2 " to set the
or
3/12