Mitsubishi Electric Mr. SLIM MSZ-FA25VA Technical Manual página 421

Ocultar thumbs Ver también para Mr. SLIM MSZ-FA25VA:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

MXZ-5A100VA
R.V. coil
Refrigerant flow in cooling
OFF
ON
Refrigerant flow in heating
O
9.52
Indoor unit
E
O
9.52
Indoor unit
D
O
9.52
Indoor unit
C
O
9.52
Indoor unit
B
O
12.7
Indoor unit
A
Indoor unit
A
Strainer
#100
Indoor unit
B
Strainer
#100
Indoor unit
C
Strainer
#100
Indoor unit
D
Strainer
#100
Indoor unit
E
Strainer
#100
MAX REFRIGERANT PIPING LENGTH
Piping length each indoor unit (a, b, c, d,e)
Total piping length (a+b+c+d+e)
Bending point for each unit
Total bending point
It does not matter which unit is higher.
Outdoor unit
Refrigerant piping length (one way, 5 unit total)
precharged
(g)
40m
4,000
0
Calculation : Xg=20g/mx(Refrigerant piping length(m)-40)
Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes,refer to the
tables below.
When diameter of refrigerant pipe is different from that of outdoor unit union, use optional Different-diameter pipe.
For further information on Different-diameter pipe,see 17-1.
Indoor unit
class
Pipe diameter
Liquid
6.35(1/4)
22/25/35
Gas
9.52(3/8)
Liquid
6.35(1/4)
50
Gas
12.7(1/2)
Liquid
6.35(1/4)
60
Gas
15.88(5/8)
Liquid
9.52(3/8)
71
Gas
15.88(5/8)
Compressor
High-pressure
switch
Oil separator
Stop valve
(with service port)
O
12
Muffler
Capillary tube
O
O
4.0
2.8 100
O
6.35
LEV A
Stop valve
Strainer
O
6.35
#100
LEV B
O
6.35
LEV C
O
6.35
LEV D
O
6.35
LEV E
50m
60m
70m
200
400
600
Extension pipe diameter
Liquid
6.35(1/4)
Gas
9.52(3/8)
Liquid
6.35(1/4)
Gas
12.7(1/2)
Liquid
6.35(1/4)
Gas
15.88(5/8)
Liquid
9.52(3/8)
Gas
15.88(5/8)
O
16
Discharge
temperature
thermistor RT62
Capillary tube
O
2.5
O
0.6 1000
4-way valve
O
16
O
16
LEV F
Power
O
receiver
8
Indoor
units
25m
80m
25
80
c
80m
d
800
Outdoor unit union diameter
For
Indoor unit A
Indoor unit B
Indoor unit C
Indoor unit D
Indoor unit E
59
Esquemas frigorífi cos
Unit:mm
O
16
Outdoor
heat
exchanger
Outdoor heat
exchanger
temperature
thermistor
RT68
Defrost
thermistor
RT61
Capillary tube
O
O
3.0
2.0 300
Strainer
Distributor
#100
a
Outdoor
b
unit
15m
10m
e
Unit : mm (inch)
Liquid
6.35(1/4)
Gas
12.7(1/2)
Liquid
6.35(1/4)
Gas
9.52(3/8)
Liquid
6.35(1/4)
Gas
9.52(3/8)
Liquid
6.35(1/4)
Gas
9.52(3/8)
Liquid
6.35(1/4)
Gas
9.52(3/8)
Ambient
temperature
thermistor
RT65
15m
421