2-4. Outdoor unit failure mode table
SUZ-KA25VA.TH SUZ-KA35VA.TH SUZ-KA25VAH.TH SUZ-KA35VAH.TH
LED indication
Abnormal point
(Outdoor unit)
(Failure mode)
1-time flash every
Outdoor thermistors
2.5 seconds
2-time flash
2.5 seconds OFF
3-time flash
2.5 seconds OFF
4-time flash
2.5 seconds OFF
5-time flash
Outdoor control
2.5 seconds OFF
system
7-time flash
Fin temperature/ P.C.
2.5 seconds OFF
board temperature
overheat
8-time flash
Converter control
2.5 seconds OFF
system
9-time flash
2.5 seconds OFF
10-time flash
Overcurrent protection
2.5 seconds OFF
11-time flash
Overcurrent protection
2.5 seconds OFF
12-time flash
2.5 seconds OFF
Lighting
Refrigerant system
High pressure
protection
Low discharge
temperature
Outdoor fan
Outdoor power
system ( )
Operation indicator lamp of the indoor unit (only the wireless remote controller use model) blinks twice.
Refer to 12-2-1. 3 and 12-2-3.[Outdoor pattern B].
Details of abnormal
Discharge temperature
When thermistors short or open during
Defrost thermistor
compressor running.
Ambient temperature thermistor
Fin temperature thermistor
P.C. board temperature thermistor
Nonvolatile memory data
When nonvolatile memory data cannot be
read properly, unit stops.
Fin
When fin temperature exceeds 83
temperature/ P.C. board
(SUZ-KA25VA(H))/ 82
temperature overheat
or P.C. board temperature exceeds 85
protection
(SUZ-KA25VA(H))/ 81
DC voltage
When DC voltage of inverter cannot be
detected normally.
Compressor each phase current
When compressor each phase current
cannot be detected normally.
Compressor open-phase
When 14A(SUZ-KA25VA(H))/ 24A(SUZ-
protection
KA35VA(H)) current flow into intelligent
power module(IPM).
When the
compressor is detected.
When the interphase short out occurs in
the output of the intelligent power
module(IPM).
When the compressor winding shorts out.
Overcurrent protection
When 14A(SUZ-KA25VA(H))/ 24A(SUZ-
KA35VA(H)) current flow into intelligent
power module(IPM).
Compressor synchronous
When waveform of compressor current is
abnormality
distorted.
( Compressor start-up failure
protection)
Discharge temperature overheat
When discharge temperature exceeds
116
protection
High pressure protection
When the indoor coil themistor(TH5)
(Overheat protection)
exceeds 70
When the defrost thermistor exceeds 70
in COOL mode.
Low discharge temperature
When discharge temperature has been
protection
50
Outdoor fan protection
When outdoor fan has stopped within 30
seconds 3-times in a row after outdoor fan
start-up, unit stops.
Outdoor power system
When it consecutively occurs 3 times that
the compressor stops for overcurrent
protection or start-up failure protection
within 1 minute after start-up.
Detection method
°C
°C
(SUZ-KA35VA(H)),
°C
(SUZ-KA35VA(H)).
open-phase protection of
°C
.
°C
in HEAT mode.
°C
or less for 20 minutes.
Resolución de averías
Check point
•Check the outdoor thermistors
Defective outdoor thermistors can be
identified by checking the blinking
pattern of LED.
•Replace the inverter P.C. board.
•Check around outdoor unit.
•Check outdoor unit air passage.
°C
•Check the outdoor fan motor.
•Check the inverter/compressor.
•Reconnect compressor connector.
•Check the inverter/compressor.
•Reconnect compressor connector.
•Check the inverter/compressor.
•Check the stop valve.
•Reconnect compressor connector.
•Check the inverter/compressor.
•Check the refrigerant circuit and
refrigerant amount.
•Check the LEV.
•Check the outdoor thermistors.
•Check refrigerant circuit and
refrigerant amount.
°C
•Check the stop valve.
•Check the refrigerant circuit and
refrigerant amount.
•Check the LEV.
•Check the outdoor fan motor.
•Check the inverter P.C. board.
•Reconnect compressor connector.
•Check the inverter/compressor.
•Check the stop valve.