Electrical shock hazard. Can burn or kill. If
your basement has water or moisture on floor, do not walk on
wet area until all power has been turned off. If shut-off box is
in basement, call electric company or hydro authority to shut-
off service to house, or call your local fire department for
instructions. Remove pump and repair or re place. Failure to
follow this warning can result in fatal electrical shock.
17. Pump water only with this pump. Do not use with salt
water or brine.
18. Do not install the pump in any location classified as
hazardous by the National Electric Code, ANSI/NFPA
70-2011 or the Canadian Electrical Code.
INSTAllATION
1. Install the pump in a sump pit with a minimum diameter
of 11" (279mm). The sump depth should be 20" minimum
(381mm). Construct the sump pit of tile, concrete, steel or
plastic. Check the local codes for approved materials.
2. Adjust the float stop on the rod to adjust the pump "ON"
point. "OFF" point is factory preset.
3. The pump should not be installed on clay, earth or sand
surfaces. Clean the sump pit of small stones and gravel
which could clog the pump. Keep the pump inlet screen
clear.
4. Install the pump in the pit so that the switch operating
mechanism has maximum possible clearance.
5. Install the discharge plumbing. When using rigid pipe,
use plastic pipe. Wrap the threads with PTFE pipe thread
sealant tape. Screw the pipe into the pump hand tight
plus 1 to 1-1/2 turns.
NOTICE: Do not use ordinary pipe joint compound on
plastic pipe. Pipe joint compound can attack plastics and
damage the pump.
Risk of flooding. If a flexible discharge
hose is used, make sure the pump is secure in the sump
to prevent movement. Failure to secure the pump may
allow pump movement, switch interference and prevent
the pump from starting or stopping.
6. To reduce motor noise and vibrations, a short length of
rubber hose (e.g. radiator hose) can be connected into
the discharge line near the pump using suitable clamps.
7. Install an in-line check valve to prevent backward flow
through the pump when the pump shuts off.
8. Power Supply: The pump is designed for 115 V., 60 Hz.,
operation and requires a minimum 15 amp individual
branch circuit. The pump is supplied with a 3-wire cord
set with grounding-type plug. Do not modify cord or
plug. Be sure it is connected only to a properly grounded
grounding-type receptacle.
Hazardous voltage. Can shock, burn or
kill. The pump should always be electrically grounded to
a suitable electrical ground such as a grounded water
pipe or a properly grounded metallic raceway, or ground
wire system. Do not modify the cord or plug or cut off the
round ground pin.
9. If the pump discharge line is exposed to an outside sub-
freezing atmosphere, the portion of the line exposed must
be installed so any water remaining in the pipe will drain
to the outfall by gravity. Failure to do this can cause the
water trapped in the discharge to freeze which could
result in damage to the pump.
10. After the piping and check valve have been installed, the
unit is ready for operation.
11. Check the operation by filling the sump with water and
observing pump operation through one complete cycle.
Risk of Flooding. Failure to make this
operational check may lead to improper operation,
premature failure, and flooding.
OPERATION / MAINTENANCE
Risk of electrical shock. Can burn or cause
death. Do not handle a pump or pump motor with wet hands
or when standing on a wet or damp surface, or in water.
Before attempting to check why unit has stopped operating,
disconnect power from unit.
Risk of fire and explosion. Can cause
severe injury, property damage or death. Do not use in
explosive atmospheres. Pump water only with this pump.
1. The shaft seal depends on water for lubrication and
cooling. Do not operate the pump unless it is submerged
in water as the seal may be damaged if allowed to run
dry.
2. The motor is equipped with an automatic reset thermal
protector. If the temperature in the motor should rise
unduly, the switch will cut off all power before damage
can be done to the motor. When the motor has cooled
sufficiently, the switch will reset automatically and restart
the motor. If the protector trips repeatedly, the pump
should be removed and checked as to cause of difficulty.
Low voltage, long extension cords, clogged impeller, very
low head or lift, etc., could cause cycling.
3. The pump will not remove all water. If a pump is operating
and suddenly no water comes out of the discharge hose,
shut the unit off immediately. The water level is probably
very low and the unit has broken prime.
SWITCH REPlACEMENT
1. Disconnect power to the pump.
2. Remove the pump from the sump. If it is in effluent
service, disinfect it for one hour with chlorine bleach.
Wear rubber gloves when handling the pump.
3. Remove the bottom tether strap from the float rod, lift
the float and swing it sideways, and remove it from the
switch arm.
4. Remove the four screws that secure the switch to the top
of the motor housing and lift the switch off the motor. The
switch guard may come off with it.
5. Disconnect four wires that connect the switch to the motor
housing.
6. Remove and discard the gasket between the switch
and the pump. Clean the gasket surface on the motor
housing.
7. Set the new gasket on the motor housing, then connect
the four wires on the new switch to the four terminals in
the motor housing (see Figure 1, page 4). Do not disturb
the two spade terminals on the switch!
NOTICE: When you connect the two power wires to the
cord terminals, make sure that the wire ends don't lodge
between the cord pin and the side of the cord plug. The
connector must be on the pin.
8. With the switch guard in place, set the switch on the
motor housing with the switch arm pointed toward the
discharge side of the pump and install and tighten the
four screws which secure the switch to the pump.
9. Holding the float out sideways, hook the float rod on to
the switch arm and swing the float rod down.
3