Notes: * Operation temperature of indoor unit.
Cooling mode: 15 °C WB - 24 °C WB
Heating mode: 15 °C DB - 27 °C DB
*1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling: Indoor: 27 °C DB/19 °C WB
Heating: Indoor: 20 °C DB
*2 The figure in ( ) indicates panel's.
*3 The external static pressure is set to 20 Pa at factory shipment.
*4 The external static pressure is set to 50 Pa at factory shipment.
*5 The external static pressure is set to 15 Pa at factory shipment.
*6 The figure in < > indicates noise level at 240 V/50 Hz.
*7 The figures represent a 240 V/50 Hz unit measured at a point which is 1 m away from the front of the unit and at a height of 1 m from the floor.
The noise is approximately 1 dB(A) less for a 230 V unit and approximately 2 dB(A) less for a 220 V unit. The noise is approximately 3 dB(A) less when the
measurement point is 1.5 m away from the front of the unit and at a height of 1.5 m from the floor.
*8 The operating noise is the data that was obtained in an anechoic room.
18
Outdoor: 35 °C DB
Outdoor: 7 °C DB/6 °C WB
Tabla de contenido