The appliance and its individual shut off valve must be
disconnected from the gas supply piping system during any
pressure testing of the system at test pressures in excess
of 1/2 psig (3.5kPa.).
When checking the manifold gas pressure, the inlet
pressure to the regulator should be at least 6.0" W.C. (14.9
mb) for natural gas or 11.0" W.C. (27.4 mb) for propane. Do
not attempt any adjustment of the pressure regulator.
36" Gas Inlet Location
36" Gas Inlet Location
36" Gas Inlet Location
CAUTION!
The appliance must be isolated from the gas supply
piping system by closing its individual manual shut-off
valve during any pressure testing of the gas supply
piping system at test pressures equal to or less than 1/2
psig (3.5kPa.).
Manual gas
shut-off valve
¾" (19 mm) Flex line
or
Adapter
Installer is responsible for ensuring that the installation, gas
connections, and grounding comply with all applicable
codes.
CAUTION!
Do not remove the back cover of the range. It is for an
authorized servicer access only.
¾" (19 mm) external threads
½" (12.7 mm) internal threads
or
48" Gas Inlet Location
48" Gas Inlet Location
48" Gas Inlet Location
Range
Gas Inlet
}
Adapter
Figure 13: Gas Supply Connection
English 15