10-2
Certification for the Drive
Field Wiring Terminal Markings
For correct field wiring connections that are to be made to each terminal refer to Chapter 3:
"Installing the Drive" - Wiring Guidelines.
Terminal Tightening Torque
Refer to Chapter 3: "Installing the Drive" – Terminal Tightening Torque.
Terminal/Wire Sizes
North American wire sizes (AWG) are based on NEC/NFPA-70 for ampacities of
thermoplastic-insulated (75ºC) copper conductors.
Power input and output wire sizes should allow for an ampacity of 125% of the rated input and
output amperes for motor branch-circuit conductors as specified in NEC/NFPA-70. Refer to
Chapter 3: "Installing the Drive" – Terminal Block Acceptance Sizes.
Input Fuse Ratings
If fitted, fuses should be in accordance with NEC/NFPA-70.
Drive Power
(kW/hp)
0.25/0.3
0.37/0.5
0.55/0.75
0.75/1.0
Drive Power
(kW/hp)
1.1/1.5
1.5/2.0
Drive Power
(kW/hp)
0.37/0.5
0.55/0.75
0.75/1.0
1.1/1.5
1.5/2.0
2.2/3.0
Drive Power
(kW/hp)
2.2/3.0
Drive Power
(kW/hp)
2.2/3.0
3.0/4
4.0/5
Drive Power
(kW/hp)
3.0/4
4.0/5
5.5/7.5
7.5/10
FRAME 1 : 1-Phase (IT/TN), 230V
Input Current @ 5kA
(A)
4.2
6.2
7.9
10.5
FRAME 2 : 1-Phase (IT/TN), 230V
Input Current @ 5kA
(A)
13.8
16.0
FRAME 2 : 3-Phase (IT/TN), 400V
Input Current @ 10kA
(A)
2.5
3.3
4.1
5.9
7.5
9.4
FRAME 3 : 1-Phase (IT/TN), 230V
Input Current @ 7.5kA
(A)
22.0
FRAME 3 : 3-Phase (IT/TN), 230V
Input Current @ 7.5kA
(A)
14.3
18.1
23.1
FRAME 3 : 3-Phase (IT/TN), 400V
Input Current @ 10kA
(A)
11.1
13.9
18.0
23.6
Supply Fuse Rating (A)
10 x 38mm
10
10
10
15
Supply Fuse Rating (A)
10 x 38mm
20
20
Supply Fuse Rating (A)
10 x 38mm
10
10
10
10
10
15
Supply Fuse Rating (A)
10 x 38mm
30
Supply Fuse Rating (A)
10 x 38mm
20
25
30
Supply Fuse Rating (A)
10 x 38mm
15
20
25
30
650 Series AC Drive