Trips and Fault Finding
ID
Trip Name
18
CURRENT LIMIT
21
LOW SPEED OVER I
22
10V FAULT
24
DESATURATION
25
DC LINK RIPPLE
26
BRAKE SHORT CCT
28
ANOUT FAULT
29
DIGIO 1 (T9)
FAULT
30
DIGIO 2 (T10)
FAULT
31
UNKNOWN
33
ICAL
-
Product Code Error Switch unit off/on. If persistent, return unit to factory
-
Calibration Data
Error
-
Configuration Data
Error
Possible Reason for Trip
Software overcurrent trip:
If the current exceeds 180% of stack rated current for a
period of 1 second, the drive will trip. This is caused by
shock loads. Remove the shock load.
ACCEL TIME and/or FIXED BOOSTset too high
DECEL TIME set too low
The motor is drawing too much current (>100%) at zero
output frequency:
FIXED BOOST level set too high
10V fault:
+10V REF overload warning (terminal 4) -
10mA maximum
Desaturation:
Instantaneous overcurrent. Refer to OVERCURRENT in
this table.
The dc link ripple voltage is too high:
Check for a missing input phase
Brake resistor overcurrent:
Check brake resistor value is greater than minimum
allowed
AOUT overload on terminal 5:
10mA maximum
DIN3 overload on terminal 9:
20mA maximum
DOUT2 overload on terminal 10:
50mA maximum
Unknown trip
Zero I Current Calibration:
Current sensor calibration fault. Switch unit off/on. If
persistent, return to factory.
Switch unit off/on. If persistent, return unit to factory
Press the
key to accept the default configuration. If
persistent, return unit to factory