Perating The; Pre-Operation Checks; Initial Start-Up Routines; Rive - Parker 650 Serie Manual De Producto

Tabla de contenido
O

PERATING THE

1

Pre-Operation Checks

Wait for 5 minutes after disconnecting power before working on any part of the system or removing the
Initial checks before applying power:
Check for damage to equipment.
Mains power supply voltage is correct.
Motor is of correct voltage rating and is connected in either star or delta, as appropriate.
Check all external wiring circuits - power, control, motor and earth connections.
Completely disconnect the drive before point to point checking with a buzzer, or when checking
Note:
insulation with a Meggar.
Check for loose ends, clippings, drilling swarf etc. lodged in the drive and system.
If possible check that the motor can be turned freely, and that any cooling fans are intact and free from obstruction.
Ensure the safety of the complete system before the drive is energised:
Ensure that rotation of the motor in either direction will not cause damage.
Ensure that nobody else is working on another part of the system which will be affected by powering up.
Ensure that other equipment will not be adversely affected by powering up.
Prepare to energise the drive and system as follows:
Remove the supply fuses, or isolate using the supply circuit breaker.
Disconnect the load from the motor shaft, if possible.
If any of the drives control terminals are not being used, check whether these unused terminals need to be tied high
or low.
If the motor thermistor terminals are not connected to a motor thermistor, connect these terminals together.
Check external run contacts are open. Check external speed setpoints are all zero.
Re-apply power to the drive and system

Initial Start-up Routines

Note:
!
!
IMPORTANT
When power
is applied to
IMPORTANT
the drive in
On power-up
Remote
in Remote
Control, it will
Control, the
immediately
drive will
start running if
immediately
the RUN
start running if
signal is
the RUN
active.
signal is
Note:
650 Series AC Drive
D

RIVE

terminal cover from the drive.
Refer to Chapter 5: "Using the Keypad" to familiarise yourself with the keypad's
indications, and how to use the keys and menu structure.
Unpredictable motion, especially if motor parameters are incorrect.
Ensure no personnel are in the vicinity of the motor or any connected machinery.
Ensure that machinery connected to the motor will not be damaged by
Ensure that the emergency stop circuits function correctly before running the motor
The drive can be started in either Remote Control or Local Control. By default, the drive will
start in Local Control.
These routines assume that the drive's control terminals are wired as shown in the Control
Wiring Connections in Chapter 3.
Connected in this way, a positive setpoint will rotate the motor in a clockwise direction when
viewed down the shaft, looking toward the motor.
If during the start-up routine the display shows either an alarm
(indicated by the letter "A") or a flashing Warning message,
refer to Chapter 7: "Trips and Fault Finding".
WARNING!
WARNING!
unpredictable motion.
for the first time.
Operating the Drive
A typical alarm
4-1
Tabla de contenido
loading

Tabla de contenido