Installation Instructions
Determining the fuse
US
Determine which fuse can be provided as a maximum
in your distribution box.
The Wall Charger Connect has an internal I Sel rotary
FC
switch, with which the maximum current can be
limited. The table shows the required fuse and the
ESM
corresponding setting of the rotary switch.
Switch position
Fuse to be used
F
100 A
E
80 A
D
60 A
C
50 A
B
40 A
A
30 A
9
25 A
8
20 A
7
15 A
6
15 A
If the Wall Charger Connect is to be operated in a
mode above 60 A, an external on/off switch must be
installed in the supply cable. This switch must be
fitted at an easily accessible place. As a minimum
requirement, the Off switch position must be
lockable.
f Please see chapter "Setting the maximum current
(I Sel)" on page 19.
16
Selecting the installation location
Electric shock, fire
DANGER
Improper use of the charger or non-compliance with
the safety instructions can cause short circuits,
electric shocks, explosions, fires or burns.
e Do not install the Wall Charger Connect in
potentially explosive atmospheres.
e Before installing the Wall Charger Connect, make
sure that there are no electric wires in the area in
which the mounting holes are to be drilled.
e To reduce the risk of explosion, particularly in
garages, make sure that the control unit is at least
19.7 in. (50 cm) above the floor during charging.
e Observe the locally applicable electrical
installation regulations, fire protection measures,
accident prevention regulations and escape
routes.
The Wall Charger Connect is designed for installation
indoors and outdoors. The following criteria must be
considered when selecting a suitable installation
location:
– If possible, install the connection and the Wall
Charger Connect in a covered area away from
direct sunlight and rain (e.g. in a garage). Direct
sunlight can lead to a reduced charging power or
cause the charging process to be switched off.
– Do not install the Wall Charger Connect under
hanging objects.
– Do not install the Wall Charger Connect in
stables, livestock buildings or locations where
ammonia gases occur. Also, do not operate the
charger in these locations.
– Install the Wall Charger Connect on a smooth
surface.
– The Wall Charger Connect is designed for
installation on walls. In order to ensure secure
fastening, check the condition of the wall before
installation. Make sure that the wall on which the
Wall Charger Connect is to be installed is
sufficiently stable to hold 88 lbs (40 kg) in
weight.
– Install the Wall Charger Connect as close as
possible to the preferred parking position for the
vehicle. Take the orientation of the vehicle into
account.
– Install the Wall Charger Connect so that it is not
near pathways and the cables do not cross any
pathways.
– Please note: When charging with high currents,
the Wall Charger Connect can heat up. Make sure
that the Wall Charger Connect is installed in a
well-ventilated place.
– The Wall Charger Connect has a charging cable
measuring 14.8 feet (4.5 m). Make sure that you
can reach the charging socket of your vehicle
without putting tension on the cable.
– Make sure that the Wall Charger Connect is
installed such that the parking position of the
charging plug is between 2 feet and 4 feet
(60 cm and 120 cm) above the ground.