2. Safety
Application (see table page 11):
Example 1
Sensor type Pt100, configured measuring range = -50 ... +100 °C, so configured
measuring span = 150 K.
GB
This is not smaller than 84 K. Thus the Total Safety Accuracy is 2 % FS,
thus 2 % * 150 K = 3 K,
and/or 2 % * 16 mA = 320 μA in terms of the current output
Example 2
Sensor type Pt100, configured measuring range = 0 ... 50 °C, so configured
measuring span = 50 K
This is smaller than 84 K, thus the total safety accuracy is 2 K,
thus 2 K / 50 K = 4 %, and 4 % * 16 mA = 640 μA in terms of the current output

2.7 Configuration changes

WARNING!
During the configuration change, the safety function is not active! Safe
operation is only admissible with activated write protection (password).
Carry out configuration changes within the permissible specifications in accordance
with chapter "2.1 Intended use in safety applications".
With the supplied configuration tools, the write protection, and other items, for the
model T32.xS is settable:
WIKA T32 Configuration Software
AMS

SIMATIC PDM

DTM (from Version DTM Beta version V1.0.2, January 2003) in conjunction with
operating software to the FDT/DTM Standard, e.g. PACTware, FieldMate
HART
®
hand-held terminal FC475, FC375, MFC4150
WARNING!
The safety function must be checked following any configuration
procedure.
12
WIKA safety manual temperature transmitter T32.xS