Configuration Changes; Simatic Pdm - WIKA T32. S Serie Manual De Seguridad

Transmisores de temperatura
Ocultar thumbs Ver también para T32. S Serie:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

2. Safety
Application (see page12):
Example 1
Sensor type Pt100, configured measuring range = -50 ... +100 °C,
so configured measuring span = 150 K
This is not smaller than 84 K. Thus the total safety accuracy is 2 % FS,
so 2 % * 150 K = 3 K, or 2 % * 16 mA = 320 μA in terms of the current output
Example 2
Sensor type Pt100, configured measuring range = 0 ... 50 °C,
so configured measuring span = 50 K
This is smaller than 84 K, thus the total safety accuracy is 2 K,
thus 2 K / 50 K = 4 %, and 4 % * 16 mA = 640 μA in terms of the current output

2.7 Configuration changes

WARNING!
During the configuration change, the safety function is not active! Safe
operation is only admissible with activated write protection (password).
Carry out configuration changes within the permissible specifications in accordance with
chapter 2.1 "Intended use in safety applications".
With the supplied configuration tools, such items as the write protection for model T32.xS
can be set:
Configuration software WIKA_T32
AMS

SIMATIC PDM

DTM in conjunction with operating software to the FDT/DTM Standard, e.g. PACTware,
FieldMate
HART
hand-held terminal FC475, FC375, MFC4150, MFC5150
®
WARNING!
The safety function must be checked by testing following any configuration
procedure.
WIKA safety manual temperature transmitter T32.xS
EN
13