baltur TBL 85P Manual De Instrucciones página 12

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 71
PIPES FOR LIGHT OIL BURNER MODEL TBL 130P/ P DACA - 160P/ P DACA - 210P
E
N
G
L
I
S
H
1 Tank
3 Wire-net filter
4 Pump
6 Suction pipe
7 Return pipe
10 Bottom valve
GRAVITY SUPPLY SYSTEM
1 Tank
2 Feeding pipe
3 Wire-net filter
4 Pump
5 Degasifier
6 Suction pipe
PUMP AXIS
DROP-TYPE SYSTEM WITH SUPPLY FROM THE TANK TOP
1 Tank
3 Wire-net filter
4 Pump
6 Suction pipe
7 Return pipe
PUMP AXIS
SUCTION - TYPE FEEDING SYSTEM
PUMP AXIS
N.B. For any missing devices
in the piping, follow existing
regulations.
0006081322_201101
7 Return pipe
8 Automatic fuel interception
device at burner shut off
9 Non-return valve
H
meters
1
1,5
2
2,5
3
8 Automatic fuel interception device at
burner shut off
9 One-way valve
10 Bottom valve
H
meters
1
1,5
2
2,5
3
H
meters
0,5
1
1,5
2
2,5
3
3,5
H = Difference in level between level in the tank and the pump axis.
L = Maximum length of suction pipe including the vertical lift.
For each bend or valve deduct 0,25 m.
6 / 20
Total meters
meters
Ø i. 16 mm.
40
45
45
50
50
Total meters
meters
Ø i. 16 mm.
40
45
45
50
50
P = 3,5 m. (max.)
Total meters
meters
Ø i. 14 mm.
Ø i. 16 mm.
36
55
30
48
25
41
20
32
15
24
10
15
4
7,5
Tabla de contenido
loading

Este manual también es adecuado para:

Tbl 105pTbl 130pTbl 160pTbl 210pTbl 85p dacaTbl 105p daca ... Mostrar todo

Tabla de contenido